Chapter 5 Operating SCU 45
ACTURA Flex 48330
Power System User Manual
Serial
No.
Alarm
Description
Default
alarm level
Default
related
relay
Related parameter
configuration
36 Batt4
Failure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical None
37 Batt1
Over-curr
The charge current of battery group 1
is bigger than the set value of
parameter “Over”
Observation
None
38 Batt2
Over-curr
The charge current of battery group 2
is bigger than the set value of
parameter “Over”
Observation
None
39 Rect Vac Err
All AC voltages are lower than the
AC low-volt point
Major 3
40 Rect
Over
Temp
Rectifier internal temperature higher
than 90°C
Observation
None
41 Rect
Failure
Rectifier over-voltage, higher than
rectifier high threshold
Critical 3
42 Rect
Protect
AC over-voltage (
ƒ
295V) or
under-voltage ( 80V)
Observation
3
43 Rect Fan Fails
Fan faulty
Major
3
44 Rect
PowerLimit
AC voltage lower than 176V, with
rectifier internal higher than 85°C or
temperature at inlet higher than 45°C
Observation
3
45 Rect Com Failure
Rectifier and monitoring module
communication interrupted
Major 3
46 Multi Rect Fail
More than 2 rectifiers raised alarms Critical
None
47 Self-detect
error
Error is detected through hardware
self-detection
No alarm
None
48 Manual
Mode
Battery management in the manual
state
No alarm
None
49 Non-FC
Status
Including auto-BC, Cyclic Boost,
constant current test and short test
No alarm
7
50 Batt Discharge
Battery being discharging
No alarm
None
51 Curr
Imbalance
In a system with load shunt, the
detected load current plus battery
current differs sharply from the
rectifier output current
No alarm
None
Not existent in this
power system series
52 Batt
Test
Error
Battery discharge time unexpectedly
short
Observation
None
53 Short
Test
Fault
During the short test, the two
batteries discharged more than the
set value
Observation
None
54 Outvolt
Fault
The maintenance FC voltage
different from the busbar voltage, or
the reported data. The difference is
more than 1V
Observation
None
55 System
Maintain
The pre-set system maintenance
time is due
Observation
None
56 Alarm
Block
Alarms sent to the host are blocked,
valid in EEM-M protocol
No alarm
None