background image

Type 99

8

this recommendation due to the pipe arrangement, it 

may be better to make the control line tap nearer the 

regulator outlet rather than downstream of a block 

valve.  Do not make the tap near any elbow, swage, or 

nipple which might cause turbulence.

In many instances, it will be necessary to enlarge the 

downstream piping to keep flow velocities within good 

engineering practices.  Expand the piping as close to 

the regulator outlet as possible.

!

WaRnIng

Adjustment of the pilot control spring to 

produce an outlet pressure higher than 

the upper limit of the outlet pressure 

range for that particular spring can cause 

personal injury or equipment damage 

due to bursting of pressure-containing 

parts or the dangerous accumulation 

of gases if the maximum actuator 

emergency casing pressure in the 

Specifications section is exceeded.  If the 

desired outlet pressure is not within the 

range of the pilot control spring, install a 

spring of the proper range according to 

the Maintenance section.

Each regulator is factory-set for the pressure setting 

specified on the order.  If no setting was specified, outlet 

pressure was factory-set at the midrange of the pilot 

control spring.  In all cases, check the control spring 

setting to make sure it is correct for the application.

Startup

Key numbers are referenced in Figure 9 for a low or 

high pressure pilot and in Figure 12 for an extra high 

pressure pilot.  With proper installation completed and 

downstream equipment properly adjusted, perform the 

following procedure while using pressure gauges to 

monitor pressure.
  1.  Very slowly open the upstream block valve.
  2.  Slowly open the hand valve (if used) in the control 

 

       line.  The unit will control downstream pressure 

 

       at the pilot control spring setting.  See the 

 

       adjustment paragraph following these numbered  

       steps if changes in the setting are necessary during  

       the startup procedure.
  3.  Slowly open the downstream block valve.
  4.  Slowly close the bypass valve, if any.
  5.  Check all connections for leaks.

The only adjustment on the regulator is the reduced 

pressure setting affected by the pilot control spring 

(key 43, Figure 9 or 11).  Remove the closing cap 

assembly (key 46, Figure 9) and turn the adjusting 

screw (key 45, Figure 9 or 11).  Turning the adjusting 

screw clockwise into the spring case increases the 

controlled or reduced pressure setting.  Turning 

the screw counterclockwise decreases the reduced 

pressure setting.  Always replace the closing cap, if 

used, after making the adjustment.

Shutdown

Isolate the regulator from the system.  Vent the 

downstream pressure first; then vent inlet pressure to 

release any remaining pressure in the regulator.

Maintenance

Regulator parts are subject to normal wear and must be 

inspected and replaced as necessary.  The frequency 

of inspection and replacement of parts depends on the 

severity of service conditions or the requirements of 

local, state, and federal rules and regulations.

!

WaRnIng

Avoid personal injury or damage to 

property from sudden release of pressure 

or uncontrolled gas or other process fluid. 

Before starting to disassemble, isolate 

the pilot or regulator from all pressure 

and cautiously release trapped pressure 

from the pilot or regulator.  Use gauges to 

monitor inlet, loading, and outlet pressures 

while releasing these pressures.

On reassembly of the regulator, it is recommended 

that a pipe thread sealant be applied to pressure 

connections and fittings as indicated in Figures 7 

and 9 and lubricant be applied to sliding and bearing 

surfaces as indicated in Figures 7 and 9, and that an 

anti-seize compound be applied to adjusting screw 

threads and other areas indicated Figures 9 and 11.

actuator and Standard P590 Series Filter

This procedure is to be performed if changing the main 

spring and spring seat for those of a different range, 

or if inspecting, cleaning, or replacing any other parts.  

Unless otherwise indicated, part key numbers for a 

Type 99 regulator with low or high pressure pilot and 

Содержание 99

Страница 1: ... H110 pop relief valve The pilot supply regulator reduces inlet pressure to a usable 200 psig 13 8 bar for the extra high pressure pilot This regulator comes standard with O ring seals on the guide bushing and valve carrier key 26 Figure 7 to keep main valve body outlet pressure from interfering with outlet pressure in the lower casing assembly key 29 Figure 9 Specifications Warning Since a pilot ...

Страница 2: ...ber Color Code Wire Diameter Inches cm Free Length Inches cm 61L 400 27 6 2 to 4 inches w c 3 to 12 inches w c 0 25 to 2 psig 1 to 5 psig 2 to 10 psig 5 to 15 psig 10 to 20 psig 5 to 10 mbar 7 to 30 mbar 0 02 to 0 14 bar 0 07 to 0 34 bar 0 14 to 0 69 bar 0 34 to 1 03 bar 0 69 to 1 38 bar 1B558527052 1C680627222 1B886327022 1J857827022 1B886427022 1J857927142 1B886527022 Orange Unpainted Red Yellow...

Страница 3: ...he main diaphragm E through the downstream control line Figure 2 Schematic of Type 99 Regulator with Type 61L Low Pressure Pilot In operation assume the outlet pressure is less than the setting of pilot control spring A The top side of pilot diaphragm assembly F will have a lower pressure than the setting of spring A Spring A forces the diaphragm head assembly upward opening the relay or inlet ori...

Страница 4: ...his diaphragm opposes the force of the pilot control spring A Monitoring Systems Monitoring regulators serve as overpressure protection devices to limit system pressure in the event of open failure of a working regulator feeding the system Two methods of using Type 99 regulators in monitoring systems are as follows Working Monitor On a working monitor installation Figure 4 the control line of the ...

Страница 5: ...must have an O ring seal on the valve carrier assembly This seals off the leak path that otherwise would let line pressure ahead of the working regulator inlet try to close the wide open monitoring regulator Figure 4 Working Monitor Installation Figure 5 Typical Wide Open Monitor Installations Flexible arrangement that permits wide open monitor to be either upstream or downstream Flexible arrangem...

Страница 6: ...r should be inspected for damage periodically and after any overpressure condition Warning The 1000 psig 69 0 bar maximum inlet regulator must not be used on hazardous gas service unless the Type H110 relief valve can be vented into a safe area If vented gas can accumulate and become a hazard in enclosed conditions such as in a pit underground or indoors the relief valve must be repiped to carry t...

Страница 7: ...g key 24 Figure 9 or 11 However as long as the 1 4 inch NPT tapping in the main valve body is plugged this tubing may be disconnected from both the main valve and filter assembly key 75 Figure 9 in order to install a pilot supply line from a desired remote location into the filter If the maximum pilot inlet pressure will be exceeded by main valve pressure install a separate reducing regulator if n...

Страница 8: ...e 3 Slowly open the downstream block valve 4 Slowly close the bypass valve if any 5 Check all connections for leaks The only adjustment on the regulator is the reduced pressure setting affected by the pilot control spring key 43 Figure 9 or 11 Remove the closing cap assembly key 46 Figure 9 and turn the adjusting screw key 45 Figure 9 or 11 Turning the adjusting screw clockwise into the spring cas...

Страница 9: ...9 away from the valve body key 17 Figure 9 with a disk or O ring seat the valve carrier must be pulled out of the lower casing to gain access to the O ring Another O ring held captive by the pressed in bushing is part of the lower casing assembly on a stem seal unit and normally does not require replacement 8 If clogging is suspected in the upstream regulator passages disconnect the pilot supply t...

Страница 10: ...d in the body Note Before putting the relay spring case over the diaphragm make certain the yoke is square with respect to the prong in the relay body The yoke can bind on the prong if it is not square 7 Use care in reassembly to be sure the edges of the diaphragms slip properly into the recess on the lower casing and relay valve body With the pilot in place check to see if it can be rocked If it ...

Страница 11: ...anging from a low to high pressure pilot or vice versa everything below the lower pilot diaphragm key 40 Figure 9 except the cap screws and the hex nut keys 47 and 13 Figure 9 will need to be replaced Actuator and main valve parts may remain unchanged unless a change in service conditions requires a change in seat construction main spring or main spring seat See the Parts List sections for obtaini...

Страница 12: ...orifice R99HPX00012 1 1 8 inch 28 6 mm orifice R99HPX00022 Travel Indicator Assembly Figure 6 Key Description Part Number Complete Assembly includes individual parts listed below 20A7146X0C2 1 Spring Case Cast iron 2L296219012 101 Indicator Stem Adaptor Aluminum 1R395909012 102 Indicator Cap Aluminum 1L290809012 103 Indicator Stem Aluminum 1L296509022 104 Disk Nut Plastic 1F730506992 105 Machine S...

Страница 13: ... 1C2546X0012 2 inch DN 50 CL125 FF flanged Cast iron 2D986519012 2 inch DN 50 CL250 RF flanged Cast iron 2D986619012 Key Description Part Number 17 Valve Body continued 2 inch DN 50 CL150 RF flanged Steel 2E275622012 2 inch DN 50 CL300 RF flanged Steel 2E275722012 18 Holder for Type 99 regulator Disk seat Brass 1B884314012 316 Stainless steel 1B884335072 O ring Seat 7 8 inch 22 2 mm orifice Brass ...

Страница 14: ...omplete Regulator showing Type 61L pilot and disk seat 1 4 inch 6 35 mm vent shown 90 counterclockwise from normal pts pts lub AS pts pts control line tap other tap 180 opposite pts AS pts AS AS AS Apply ANti seize compound pts Apply pipe thread sealant LUB Apply Lubricant o ring set detail DJ6642 DJ6642_B ...

Страница 15: ...Type 99 15 Figure 9 Type 99 Regulator with Type 61L Low or 61H High Pressure Pilot continued Pilot Relay and cover Assembly High Pressure Pilot Parts C0289 1C 30A6800 ...

Страница 16: ...d 1B8850X0012 Cotter Pin for Stainless steel trim 316 Stainless steel 2 required 1A866537022 Key Description Part Number 29 Lower Casing Cast iron Standard 4B983719012 For use with optional protector spring washer and machine screw keys 61 62 and 63 2N379419012 Lower Casing Assembly for use with O ring stem seal Cast iron with SST guide bushing Complete with Nitrile NBR O ring 2R7230000A2 Complete...

Страница 17: ... Key Description Part Number 13 Hex Nut Plated steel 13 required 1A340324122 23 Elbow 2 required Brass 15A6002X292 316 Stainless steel 15A6002X612 24 Pilot Supply Tubing disk or O ring main valve seat Copper 1D8793000A2 Copper for oxygen service 0500201701W 316 Stainless steel 0500213809W 30 Upper Relay Diaphragm Nitrile NBR 1B885202052 Fluorocarbon FKM 1N162802332 31 Upper Relay Diaphragm Plate P...

Страница 18: ...carbon FKM 1B8868X0012 303 Stainless steel Fluorocarbon FKM 1B8868X0022 49 Bleed Valve Spring Stainless steel For use with low pressure pilot with relay orifice 1D373735032 or bleed valve 1H951635132 1E643637022 For use with all low and high pressure pilots Inlet pressure up to 250 psig 17 2 bar 1C911537022 Inlet pressure over 250 psig 17 2 bar 1N859137022 50 Bleed Valve Stainless steel For use wi...

Страница 19: ...mber 34 Connector 3 required For use with all standard regulators Brass 1D692214012 316 Stainless steel 15A6002X602 For use with 1000 psig 69 0 bar maximum inlet regulator Steel 15A6002XW22 35 Cap Screw Plated steel 6 required 1A930424052 36 Elbow Plated steel 1B860828992 37 Yoke Cap 416 Stainless steel 13A9837X012 38 Inlet Orifice 303 Stainless steel 1D318135032 39 Pilot Body Cast iron 33A9845X01...

Страница 20: ...regulators Type 61HP Extra High Pressure Pilot Figure 12 continued Key Description Part Number 45 Adjusting Screw Plated carbon steel Standard 1C216032992 47 Cap Screw Plated steel 8 required 1B787724052 49 Relief Valve Spring 316 Stainless steel 1C374037022 50 Relief Valve Plug 316 Stainless steel 1K377535162 52 Bleed Orifice Brass 1B329014012 53 Loading Tubing For use with all standard regulator...