4-7
Hardware and Software Maintenance and Troubleshooting
Figure 4-2. Signal Flow
TP1
TP1 is the vortex shedding signal after it has gone through the charge
amplifier and low pass filter stages and into the input of the sigma delta
A-to-D converter ASIC in the electronics. The signal strength at this point
will be in the mV to Volt range.
TP1 is easily measured with standard equipment.
Figures 4-3, 4-4, and 4-5 show ideal (clean) waveforms and waveforms
that may cause the output to be inaccurate. Please consult the factory if
the waveform you detect is not similar in principle to these waveforms.
88
00
-0
5
7
2D
Sensor
Charge
Amplifier
Amplifier/
Low Pass
Filter
A-to-D Converter
Containing Frequency
Generator
External
Test
Frequency
Input
TP1
Shedding Frequency Output
Digital Filter
Microprocessor
Содержание 8800A
Страница 1: ...Model 8800C and Model 8800A Smart Vortex Flowmeter 00809 0100 4003 English Rev JA ...
Страница 2: ......
Страница 4: ...Rosemount Model 8800C Vortex Flowmeter ...
Страница 8: ...Rosemount Model 8800C Smart Vortex Flowmeter 4 ...
Страница 10: ...Rosemount Model 8800C Vortex Flowmeter 1 2 ...
Страница 48: ...Rosemount Model 8800C Vortex Flowmeter 2 38 ...
Страница 74: ...Rosemount Model 8800C Vortex Flowmeter 3 26 ...
Страница 102: ...Rosemount Model 8800C Vortex Flowmeter 4 28 ...
Страница 128: ...Rosemount Model 8800C Vortex Flowmeter B 2 ...
Страница 129: ...B 3 Approvals ...
Страница 130: ...Rosemount Model 8800C Vortex Flowmeter B 4 ...
Страница 131: ...B 5 Approvals ...
Страница 132: ...Rosemount Model 8800C Vortex Flowmeter B 6 ...
Страница 133: ...Appendix C 1 Appendix C HART Communicator Connections and Hardware page C 6 ...
Страница 142: ...Rosemount Model 8800C Vortex Flowmeter C 10 ...
Страница 159: ......