Close Rate
Rate at which the HPV will close in safety mode
30
0 to 600
Seconds
HPV% Open Fail-SC
Valve % open during Subcritical with sensor failure
0
0 to 100
%
HPV% Open Fail-TC
Valve% open during Transcritical with sensor failure
0
0 to 100
%
HPV% Open Fail-Lo
Valve% minimum opening during low pressure safety
mode
15
0 to 100
%
BGV% Open Fail
Valve% open during high pressure safety mode
0
0 to 100
%
TransMaxTime
Transition time of the two Sub and Trans PID
180
30 to 600
Seconds
Setpoints
Description
Default
Range
Unit
Table 11-1
- High Pressure CO2 Controller Ranges and Default Setpoint Parameters