28 • Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 0
3.8.2. Thermostat Stage(s) Behavior
below briefly describes the behavior of the thermostat according to the
room temperature, setpoints, and stage(s) that is or are activated.
3.8.3. Input Settings
There are 5 inputs terminal (IN1 to IN5) that can be configured. Each one has a
MODE, STATE and OFFSET Modbus parameters. Also, IN1 has a supplementary
WEIGHT Modbus parameter. These configuration registers will affect the INPUT
VALUE and CONTROL TEMPERATURE Modbus registers.
Digital
Local terminal connected to a digital switch.
Thermistor
Local terminal connected to a thermistor.
0-10V
Local terminal connected to 0-10V voltage.
Input modes are configured to the following settings and are read only.
IN1 = Thermistor (used for the Indoor temperature)
IN2 = Thermistor (used for the Outdoor temperature)
IN3 = Thermistor (used for the Supply Air temperature)
Figure 3-28
- Thermostat Behavior
IMPORTANT! The DEAD BAND MINIMUM, HYSTERESIS and STAGE DIFF
parameters have write access. A special precaution must be taken in this case because these
parameters are often linked together and some interference could occur if those parameters
are not set properly.
INPUT INx MODES
Table 3-11
- Input In Modes