trip/mechanical trip or electrical trip only). Orient the
circuit breaker over its mounting location. Re-attach the
alarm wiring and shunt wiring (if applicable) to the back
of the circuit breaker as recorded above. Wiring
diagrams are provided in
Danger! The bolts being installed in the following step
may be at system potential. Use insulated tools.
7.
Install the replacement circuit breaker into its mounting
position and secure with the hardware previously
removed. Torque to 60 in-lbs.
8.
Transfer the circuit breaker guard from the old circuit
breaker to the new circuit breaker.
9.
Operate the replacement circuit breaker to the ON
position.
10.
Verify no Circuit Breaker Alarms are active.
11.
Close the distribution cabinet’s front door. Turn the latch
clockwise to secure the door.
Danger