MultiFlex I/O Board Pulse Limits - Standalone Version Only
Energy Meter Standard MODBUS Default Settings • 25
13 Energy Meter Standard MODBUS
Default Settings
Setting
Value
Modbus
Register
Setup Password
00000
–
Reset Password
00000
–
System Type
40 (3 + N) Wye
130
CT Primary Ratio (if CTs are not included) 100A
131
CT Secondary Ratio
1V
132
PT Ratio
1:1 (none)
133
System Voltage
600 V LL
134
Max. Theoretical Power (Analog Output: full
scale (20mA or 5V))
104 kW
135
Display Mode
1 (IEEE)
137
Phase Loss
10% of System Voltage (60V), 25% Phase to Phase Imbalance 142, 143
Pulse Energy
1kWh/pulse
144
Demand: number of sub-intervals per interval 1 (block mode)
149
Demand: sub-interval length
900 sec (15 min)
150
Modbus Address
001
–
Modbus Baud Rate
19200 baud
–
Modbus Parity
None
–
Log Read Page
0
158
Logging Configuration Register
0
159
Log Register Pointer 1
1 (Real Energy MSR)
169
Log Register Pointer 2
2 (Real Energy LSR)
170
Log Register Pointer 3
29 (Reactive Energy MSR)
171
Log Register Pointer 4
30 (Reactive Energy LSR)
172
Log Register Pointer 5
37 (Real Demand)
173
Log Register Pointer 6
38 (Reactive Demand)
174
Log Register Pointer 7
39 (Apparent Demand)
175
Log Register Pointer 8
155 (Month/Day)
176
Log Register Pointer 9
156 (Year/Hour)
177
Log Register Pointer 10
157 (Minutes/Seconds)
178
Table 13-1
-MODBUS Default Settings
Содержание 250-5000
Страница 1: ...Energy Meter Installation and Operation Manual 026 1726 Rev 2 ...
Страница 2: ......
Страница 4: ......
Страница 27: ...22 Energy Meter Installation and Operation Manual 026 1726 Rev 2 11 Alert Reset Information ...
Страница 29: ...24 Energy Meter Installation and Operation Manual 026 1726 Rev 2 ...
Страница 33: ......