INSTALLATION INSTRUCTIONS
1. MOUNTING THE FPDL-32
Remove the ballast channel cover. Mount the FPDL-32 in the ballast channel at least
away from the A.C. Ballast(s).
1
2"
/
When battery packs are remote mounted, the remote distance can not exceed
of the distance from ballast to
lamp specified by the A.C. Ballast manufacturer. For example, if the A.C. Ballast manufacturer recommends no
more than 25¡remote distance, then the battery pack should not exceed 12
. Under no circumstances should
the battery pack exceed a distance of 50¡from the lamp.
1
2
1
2
/
/
¡
2. WIRING
Refer to the wiring diagrams on the back page for the appropriate wiring of lamp(s) and ballast. Install in accordance
with the National Electrical Code and local regulations. For additional wiring diagrams consult Customer Service.
4. WIRING THE A.C. INPUT
A. The
and A.C. Ballast
be on the same branch circuit.
FPDL-32
must
B. The
requires an
A.C. Power source of either 120 or 277 volts. Select the proper voltage lead
and cap the unused lead.
unswitched
FPDL-32
C. When the
is used with a switched fixture, the A.C. Input to the
must be connected ahead of the
fixture switch. Refer to
for switched and unswitched fixture wiring diagrams.
FPDL-32
FPDL-32
Illustration 3
Page 2
CAUTION: Before installing, make certain the A.C. Power is off and the battery
connector is disconnected.
3. INSTALLING THE LIGHTED
Recessed Troffer Fixture
Illustration 1.
- Select a convenient location with proper clearance in the ballast cover and drill or
punch a / hole ( / knockout). Insert the / bushing into the hole. Push the plastic tube through the bushing.
Route the leads of the
through the plastic tube. Connect the LED wires from the unit to the
(V
to Red,
to White/Red). Push the entire assembly back into the tube until the lens collar rests against the plastic
tube. The plastic tube should be adjusted so that the
is within / of the fixture lens. The
must be visible after installation. Refer to
7
8"
1
2"
7 8"
1 4"
INDICATOR LIGHT
INDICATOR LIGHT
INDICATOR LIGHT
INDICATOR LIGHT
iolet
Brown
Strip Fixture -
Refer to Illustration 2.
Select a convenient location on the fixture so the
can be seen after installation.
Allow for proper clearance inside the fixture and drill or punch a 1/2" hole. Remove the nut from the
. Push the
housing into the 1/2" hole and secure with the nut. Connect the LED wires
from the
.
TBTS
TBTS
TBTS
TBTS
(Violet to Red, Brown to White/Red)
Illustration 1
Recessed Troffer Fixture
Illustration 2
Strip Fixture
7/8 BUSHING
FIXTURE
BALLAST CHANNEL COVER
PLASTIC TUBE
FIXTURE LENS
OBSERVE PROPER POLARITY
FIXTURE
TBTS
TBTS
FPDL-32
FPDL-32