background image

 

38 

 

B.

 

5 in 1 FUNCTION BRACKETS on RACK-MOUNT 3U DESIGN: 

 

 

(1)

 

19” Rack installation: 

Mount the 3U rack-mount in a 19-inch EIA 310 C standard rack. 

 

 

 

 

 

 

19” rack width   

 

39

(2)

 

23” Rack installation: 

Change the position of the two mounting brackets to mount the 3U rack-mount in a 
23-inch EIA 310 C standard rack. 

 

 

 

 

 

 

(3)

 

Tower installation: 

a.

 

Move the mounting brackets from the front to the side and attach the brackets by 
screws. Then let the UPS stand with the vertical direction as the below pictures 
shown. 

b.

 

Rotate the control panel unit from horizontal to vertical direction. 

 

 

23” rack width 

Содержание 4K VA 20K VA UPS

Страница 1: ...ced by harmful interference from the equipment it is recommended to use one of the following preventive measures z Place the receiving antenna in a separate location or orientation z Ensure a greater...

Страница 2: ...ide Refer servicing to qualified service personnel CAUTION Non isolated Battery supply Risk of electric shock battery circuit is not isolated from AC input hazardous voltage may exist between battery...

Страница 3: ...lation must be carried out in accordance with this manual Electrical installations must also carefully follow local legislation and regulations Only qualified personnel should conduct these installati...

Страница 4: ...ions of the batteries sends any forewarnings if replacement is needed Otherwise every 30 days of normal mode operation a battery discharge test is performed and any problems reported on the LCD displa...

Страница 5: ...e very hazardous to the operator 5 4 Storage Please adhere to the following instructions if the UPS is not installed immediately z Store the equipment as is in its original packing and shipping carton...

Страница 6: ...6 5 2 Rear panel views 4K 5KVA 120VDC Rear panel 7 6KVA Rear panel Without ISO...

Страница 7: ...8 6KVA Rear panel With ISO 9 8K 10KVA Rear panel Without ISO...

Страница 8: ...10 8K 10 KVA Rear panel With ISO 11 12KVA Rear panel ISO and With ISO...

Страница 9: ...nstalled z Be aware of UPS parameters and changing the Battery pack quantity when using the external battery cabinets see chapter 7 2 Installing UPS z Ensure that the installation site has all electri...

Страница 10: ...connections be used use connections according to chapter 6 of the manual provided with that option The connections can be referred to on the rear panel z The installation is now complete b removable j...

Страница 11: ...munications cards It can be used parallel with either the RS232 or USB ports Currently there are two cards available for the optional interface slot An SNMP WEB card allows management and monitoring o...

Страница 12: ...tput power has commenced and the LCD will display Line mode z Switch on the loads Shutting down the UPS z Shut down and turn off the loads z Push the ON OFF button on the front panel for two seconds T...

Страница 13: ...rol panel Normal display The UPS status is shown in normal display mode From here you have a choice to go to UPS meters display and the Setting display by pushing the button UPS meters display Various...

Страница 14: ...t Input Voltage range when bypass is available 10 10 15 15 20 10 15 Free Run Mode Free Run Set Select if UPS can run in Free run mode unsynchronized ON OFF ON Bypass Enable Disable at Free run mode By...

Страница 15: ...tness any alarm indication on the control panel Alarm indicators The UPS gives the following audible alarms z If UPS is on battery and the ON BATTERY LED is on UPS will beep every 5 seconds z If the b...

Страница 16: ...Low Output Voltage Constant beep Low output voltage Call the Local dealer Bus Fault 2 Beeps per second High internal DC bus Voltage Turn off protected loads Turn off UPS and call your local dealer Si...

Страница 17: ...h W ISOTR 342 x 690 x 715 13 4 x 27 2 x 28 1 342 x 690 x 878 13 5 x27 2 x34 6 342 x 863 x 905 13 5 x 34 0 x 35 6 Physical Net Weight kg lb W ISOTR 130 0 286 0 176 5 388 3 225 0 495 0 29 Shipping Weigh...

Страница 18: ...lf test adjustable battery transfer points and alarm settings Battery Battery Protection Cut off without draining any current when battery is low 31 Cold Start DC start YES Back Up Time Tower model Ab...

Страница 19: ...Receptacles Hardwire Dimensions W x D x H mm inch TBD 428 597 260 18 9 23 5 10 2 428 658 260 18 9 25 9 10 2 Net Weight kg lb TBD 86Kg 189lb 110Kg 242lb Physical Shipping Weight kg lb TBD 100Kg 220lb 1...

Страница 20: ...MPONENT INCLUDING 3U UPS 3U BATT CABINET FRONT VIEW REAR VIEW 35 2 UPS REAR PANEL COMPONENTS H TERMINAL BLOCK I BREAKER J EXTERNAL BATTERY CONNECTOR K BYPASS SWITCH L SNMP SLOT M RS232 EPO N TVSS O US...

Страница 21: ...TION a Remove the original right side panel and take apart the control panel unit Then assemble the blank right side panel b Connect the Control panel unit and Remote control port from rear side 37 c...

Страница 22: ...ge the position of the two mounting brackets to mount the 3U rack mount in a 23 inch EIA 310 C standard rack 3 Tower installation a Move the mounting brackets from the front to the side and attach the...

Страница 23: ...ting brackets from the front to the side and attach the brackets by screws Then mount the UPS to the wall as the below pictures shown 5 Installation with rear Bracket We can use bracket to support the...

Отзывы: