SYSTEM RESET TO FACTORY DEFAULT SETTING
•
Short press “
” to access system “RESET” function
•
Press “Mode” to confirm reset to factory default setting
17.
AUTO-RECOVERY
When there is an Overcurrent, Overvoltage, Under-voltage or Overheating error, the system will recover
itself automatically. If two errors happen in less than a 60 seconds interval, the auto-recovery time will
increase once. If the auto-recovery increases by 3 times, the system will direct you to the Error menu, and
will not execute the auto-recovery. The Auto-recovery page will display the error details during the first 5
seconds and the countdown details during the following 5 seconds
Press “Start/Stop” button to cancel the countdown during the auto-recovery process or to activate the auto-
recovery immediately. (Without activating the auto-run. If there is an error and the variable speed driver is
in operation, then after the auto-recovery the system will display the auto-start page. The auto-start page
will show the error details (same as auto-recovery, which will last for 5 seconds) and the countdown details)
Press “Run” to cancel the procedures and to auto-recover immediately (the default settings of the variable
speed driver will appear).