<type> = Two digit ASCII hex (one byte) type/medium of meter according to [4] section 5.8
representing the meter medium.
<version> = Two digits ASCII hex (one byte) version of the meter.
7.5.2.5 Receive Frame Counter
Data type: double-long-unsigned
This object holds the current value of the frame counter (invocation counter) needed for
encrypted communication.
The gateway will drop any message carrying a frame counter with the value less than the
gateway current value.
7.5.2.6 Channel Selection
Data type: long-unsigned
This object enables switching between all logical devices during a single association.
See 7.4.2 for more information.
7.5.2.7 Gateway Logical device name
This object is a mirror of the logical device name of the gateway and is accessible on all meter
logical devices in the gateway. This enables read of the gateway logical device name when
associating/addressing a meter logical device. See 7.5.1.4 for more information.
7.5.2.8 Meter Firmware Version
Data type: octet-string
This object holds the meter firmware version information.
7.5.2.9 Meter Manufacturer Id
Data type: octet-string
This object holds the meter manufacturer id information.
7.5.2.10
Meter Device Type
Data type: integer
This object holds the meter MBus device type information.
7.5.2.11
Standard Event Log – Event Id
Data type: long-unsigned
This object holds the event id of the last event logged to Standard Event Log.
7.5.2.12
Standard Event Log – Event Message
Data type: visible-string
This object holds the event description of the last event logged to Standard Event Log.