background image

CMa10w/CMa11w

 

Indoor temperature/humidity sensor, Wireless M-Bus

IntroductIon

CMa10w/CMa11w is a 1-way Wireless M-Bus temperature/

humidity sensor developed for indoor use. The product is 

available with (CMa10w) or without (CMa11w) LCD display. 

For more information about the product, please visit the 

Elvaco AB website, http://www.elvaco.com.

English

confIgure settIngs vIa Ldc dIspLay*

CMa10w has two different display modes: the standard mode 

and the setup mode. End-users will only have access to the 

standard mode, which displays current sensor information. 

The setup mode is entered using the SW1 push button (5) at 

the back of the product and can be used to configure settings 

for the sensor. In normal operation mode, the LCD display will 

be turned off in order to conserve battery life.

standard mode

Push button SW2 (2) on the front is used to display the next 

page, and get information about average, maximum and 

minimum values.  

MountIng

The sensor is mounted on a wall by using the holes on the 

product rear cover. 

overvIew

1. LCD display*
2. Push button (SW2)* 
3. NFC antenna 

IMportant

• 

Avoid mounting the product near supplementary heat 

sources, such as kitchen stoves, or in direct sunlight.

• 

Make sure to mount the product at least 1.5 meters 

from the floor and at least 1 meter from the nearest 

radiator.

• 

Do not mount the product on an external wall or near a 

door. If mounted over a conduit pipe, make sure that the 

pipe is filled to prevent air flow.

• 

Do not mount the sensor in a steel cabinet. Doing so 

will dramatically decrease the signal coverage.

deMountIng

To demount the sensor, carefully insert the end of a 

screwdriver in the upper part of one of the enclosure bottom 

holes, as illustrated below.

setup mode

The setup mode is entered by pressing and holding push 

button SW1 (4) for 5 seconds (when LCD display is off). When 

using the setup mode, the next page is displayed by pressing 

SW1 for 2 seconds. To configure the value of a field, press 

push button SW2 (2). If there are more than one configurable 

field on a page, push button SW1 is used to switch between 

them.

wIreLess M-bus

Upon delivery, the sensor will be deactivated with the radio 

turned off. The product will start transmitting data as soon as 

it is activated.

actIvatIon

The sensor can operate in two different modes: encrypted 

mode or unencrypted mode. Please advise your project 

manager about the best option for your specific project.

unencrypted mode

To activate the unencrypted mode:
1. 

Press and hold push button SW1 (5) for 6-10 seconds 

until the LED light (4) starts to flash quickly.

2. 

Release push button SW1.

encrypted mode

To activate the encrypted mode:
1. 

Press and hold push button SW1 (4) for at least 13 

seconds until the LED light (4) starts to flash slowly.

2. 

Release push button SW1.

operatIon

Upon activation, the sensor will begin transmitting wireless 

M-Bus telegrams in mode T1 every 6th minute. The telegrams 

contain sensor data as well as various information about the 

product status.

4. LED light
5. Push button (SW1)
6. Serial number

IMportant

• 

Make sure to verify that the product is activated by 

pressing SW1. If the product is set to encrypted mode, 

the LED light (4) will flash five times, if it is set to 

unencrypted mode, it will flash once.

IMportant

• 

If setup lock is enabled, the device cannot be unlocked 

again.

Отзывы: