CMi6160
User’s Manual English
CMi6160
User’s Manual English
page | 16 (38)
[2022-10]
v1.4
6.3.1 DIEHL METERING SHARKY & SCYLAR error codes
The error codes transported from an MCM is the status byte of the M-Bus header. Bits 71:64 of M-Bus
header.
Meaning of Error Codes
The following information is from the documentation received from Diehl Metering. It has only been
enhanced by formatting, contents is as-is straight from the document. For latest error description please
use the latest documentation available from DIEHL Metering. Table 2 corresponds to Table 7 of EN
13757-3:2013 for M-Bus.
Bit
Description
Usage
0
reserved
-
1
any application error
-
2
power low
E-8, E-9
3
permanent error
C-1, E-4
4
temporary error
E-1, E-3, E-6, E-7, leak error
5
manufacturer specific
see table below
6
manufacturer specific
see table below
7
manufacturer specific
see table below
Table 2: DIEHL error codes
Table 3 explains the position of error codes from
the User’s Manual of the meter.
Error
C-1
E-8
E-4
E-1
E-7
E-9
E-3
E-6
Leak
error
E-5
Mbus
status
Byte
0x08
0x04
0x28
0x50
0x70
0x84
0xB0
0xD0
0xF0
0x10
Prio
Highest
Lowest
Table 3: Error code positioning