Configuration
80 Operating instructions RHD
ELTROPLAN
-
REVCON
Elektrotechnische Anlagen GmbH
10
Configuration
The coding of the jumpers enables different driving possibilities and different internal
functions in accordance to specific error messages.
In the following different definitions are explained which result from the specific possi-
bilities of coding!
a) „Autostart“
Autostart means that the device is starting with a delay-time of about 1 sec. after connect-
ing mains voltage automatically ("automatically switch-on").
Coding via jumper, see figure 4.4.4.1:
J1 closed : Autostart
If the unit should not start automatically despite the phase failure control is disabled, dur-
ing the switch on process the terminals 7 and 8 have to be bridged till 4 s after switching
on. To start the feedback afterwards a short impulse has to be given on the RESET input.
b) „Switch on“ - „Switch off“
„Switch off“ means that the driving of the semiconductors and the power feedback will
be interrupted. A braking operation of the frequency inverter with power feedback is no
longer possible.
„Switch-on“ is the activation of driving the semiconductors.
c) „Storage“
The unit is equipped with an error storage where special failures can be assigned to.
Stored error messages have to be confirmed by RESET or interruption of mains supply.
"Storage" always leads to a "switch-off" and to a collective-error-relay tripping.
Содержание REVCON RHD B0 400V
Страница 46: ...Installation Operating instructions RHD 45 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 1 Enclosure 1 500 ...
Страница 47: ...Installation 46 Operating instructions RHD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 2 Enclosure 2 700 ...
Страница 48: ...Installation Operating instructions RHD 47 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 3 Enclosure 3 800 ...
Страница 49: ...Installation 48 Operating instructions RHD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 4 Enclosure 3 801 ...
Страница 52: ...Installation Operating instructions RHD 51 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 4 Diagram Case 4 ...