Electrical Installation
Operating instructions DC(S)
51
ELTROPLAN
-
REVCON
Elektrotechnische Anlagen GmbH
Legend for figure 4.4.1.1.1 (REVCON
DC(S))
1.
Fusing in accordance with this manual.
2.
It is not allowed to connect any other devices except the frequency inverter and the
power feed/feedback unit behind the main magnetic switch.
Danger!
If this is not observed, you take the risk that, in the case of switching off the mains during feed
back the power, the voltage in that sector may rise up to a dangerous level. This may destroy
the connected devices and perhaps also the inverter and/or the power feed/feedback unit. To
avoid such situation, the power feed/feedback unit is equipped with an overvoltage switch off,
but nevertheless this hint should be observed!
3.
Option RFI filter
4.
Separate fusing in accordance with DIN VDE 0298 or short circuit proof wiring.
5.
commutation choke in accordance with this manual
6.
It is absolutely necessary to install the inrush current limit circuit of the controller be-
tween the DC-output to the REVCON and the DC-bus capacitors.
7.
At these terminals one ore more controllers (even with different power ratings) may
be attached, like it shown in figure
4.5.1. Even if several controllers are attached, the
wires have to be as
short and low impedance
as possible!
8.
The „ON“ or „RESET“ signal may be initiated via terminals 11 and 12:
Terminals 11 and 12:
Positive pulse (12-24 V DC); practicable e.g. via PLC
(terminal 11 +, terminal 12 -).