PROTEM
®
D 404
29
4.0 DIP-Switch S 501
By the DIP switch S 501 you can select the respective type of sensor (refer to following table).
I
II
III
IV
channel
Channel
1
2
3
4
5
6
7
8
Switch number
ON
ON
x
x
x
x
x
x
Sensor 1 = no Sensor
ON OFF
x
x
x
x
x
x
Sensor 1 = PT100 single operation
I
OFF OFF
x
x
x
x
x
x
Sensor 1 = PT100 Logic
x
x
ON
ON
x
x
x
x
Sensor 2 = no Sensor
x
x
ON OFF
x
x
x
x
Sensor 2 = PT100 single operation
II
x
x
OFF OFF
x
x
x
x
Sensor 2 = PT100 Logic
x
x
x
x
ON
ON
x
x
Sensor 3 = no Sensor
x
x
x
x
ON OFF
x
x
Sensor 3 = PT100single operation
III
x
x
x
x
OFF OFF
x
x
Sensor 3 = PT100 Logic
x
x
x
x
x
x
ON
ON Sensor 4 = no Sensor
x
x
x
x
x
x
ON OFF Sensor 4 = PT100 single operation
IV
x
x
x
x
x
x
OFF OFF Sensor 4 = PT100 Logic
ON
switch in ON position
OFF switch in OFF position
x
switch position without effect
Information about the PT100 logic function:
All sensor inputs, which are recognised by the switch position PT100 logic, have the in the
following described function. The relays of the respective channels are equipped with a logical
combination with the active sensor. So if for two channels the logical function is active, the
adjusted thresholds are valid for both channels. The relay switches on, if the temperature of
PT100(1)
OR
PT100(2) is higher than the adjusted temperature. It switches off, if the
temperatures of PT100(1)
AND
PT100(2) are lower than the adjusted temperature. This logical
operation can be done with all of the four sensors in any combination.