Quick guide for TBA firmware V1.070

4. Starting the tester in the “Discharge” mode.

On the Select Job Mode screen 

(figure 4)

 choose the first „Discharge” 

mode

To proceed to the next screen choose „Next” by pressing the button 
[F3] .

Discharge parameters setting. 

(figure 5)

Set the required discharge current value Ir by means of the adjuster. 
This value can be corrected in the course of the battery discharge 
process.

Using the [F2] button place the cursor on „Uk” and set the final voltage 

value by means of the adjuster.

Using the [F2] button place the cursor on „Time” and set the discharge 

time by means of the adjuster.

Choose „Next” by pressing the [F3] button to proceed to the next 

screen .

Data logging screen. 

(figure 6)

Using the [F2] button place the cursor on „Data logging” and by means 

of the adjuster choose the number of memory bank where the data 
will be recorded during the battery test. You can select only the empty 
banks which is a protection against erasure of data from previous 

recordings. In order to avoid recording choose the „No” option.
Using the [F2] button place the cursor on „Period” and set the period 

of data recording by means of the adjuster.
The change of the data recording period implies the change of the 
Time of Data Recording whose value is displayed.
Deleting and saving of the banks were described in point 5 of the 
manual.

To proceed to the next screen choose „Next” by pressing the button 
[F3].

Discharge home screen. 

(figure 7)

Press the (green) [ON] button – The discharge will begin, fans cooling 

resistors will start working, too.

figure 5

figure 6

figure 7

figure 4

Содержание TBA 150

Страница 1: ...berecorded and transferred from the tester by means of a USB flash drive Table of Contents 1 Quick guide page 2 2 Description of the device dashboard page 2 3 Connecting batteries to the tester page 3 4 Starting the tester in the Discharge mode page 4 5 Starting the tester in the 5h 10h 20h Discharge mode page 6 6 Discharge of a battery with the rated voltage other than the basic voltages determin...

Страница 2: ...ate of the device Safety switch Enables immediate emergency cessation of the device operation ON Launches the discharge process OFF Temporarily halts the discharge process Adjuster Enablessettingthevalueofagivenparameter F1 F2 F3 function buttons Designed to select options on the display USB slot Enables transfer of data recorded during a test to a data carrier of pendrive type 1 2 3 4 5 6 7 8 9 T...

Страница 3: ...0 V or 220V the type of the battery is determined Figure 2 presents an exemplary screenshot after attaching a 48V battery If a battery with another rated voltage is attached to the tester figure 3 further proceeding should be conducted in accordance with point 6 Discharge of a battery with the rated voltage other than the basic voltagesdeterminedforgiventypesofbatterytesters Otherbattery NOTE In a...

Страница 4: ...xt screen Data logging screen figure 6 Usingthe F2 buttonplacethecursoron Datalogging andbymeans of the adjuster choose the number of memory bank where the data will berecordedduring thebatterytest Youcanselect onlytheempty banks which is a protection against erasure of data from previous recordings In order to avoid recording choose the No option Using the F2 button place the cursor on Period and...

Страница 5: ...heset discharge time is over figure 10 Fans work for three minutes after the end of the discharge Blowing process enables faster cooling of the resistors When the blowing time is over information about reason for the end ofthedischargewill remainonthedisplay U ifthebatteryvoltageat the Uk link achieved the set value figure 11 or t if the set discharge time was over figure 12 Press the F1 End butto...

Страница 6: ...ter set the correct number of tested cells this parameter is unavailable in the TBA 150 testers To proceed to the next screen choose Next by pressing the button F3 Data logging screen figure 15 Using the F2 button place the cursor on Data logging and by means of the adjuster choose the number of memory bank where the data will be recorded during the battery test You can select only empty bankswhic...

Страница 7: ...rge time was over t figure 19 Blowingisonfor3minutesaftertheendofthedischarge Theblowing process allows for faster cooling of resistors When the blowing time is over the display will show the information on the discharge end reason U when the set final voltage of the Vk cell achieved the set value figure 20 or t when the set discharge time was over figure 21 Press the F1 End button to return to th...

Страница 8: ...cethecursoron Uk andsetthefinalvoltage value of the battery by means of the adjuster Using the F2 button place the cursor on Time and set the discharge time by means of the adjuster To proceed to the next screen choose Next by pressing the button F3 Data logging screen figure 24 Using the F2 button place the cursor on Data logging and by means oftheadjusterchoosethenumberofmemorybankwherethedatawi...

Страница 9: ...re 27 or when the set time was over figure 28 Blowingisonfor3minutesaftertheendofthedischarge Theblowing process allows for faster cooling of resistors When the blowing time is over the display will show the information on the discharge end reason U when the Uk battery voltage achieved the set value figure 29 or t when the set discharge time was over figure 30 Press the F1 End button to return to ...

Страница 10: ...an contain 512 records Records are saved in the following time interval the period of record saving The frequency of record saving is set before the discharge process Transfer of data from the tester memory to a PC should be performed by using a USB memory stick For USB memory sticks with the capacity up to 2 GB select the FAT16 file system while formatting them For USB memory sticks with the capa...

Страница 11: ...press the F3 OK button The Logging and USB Memory screen figure 36 allows for managing therecorderbanks Selectabankbymeansoftheadjuster Therecord of the selected bank is deleted by means of the F2 Delete button Thetesterisequippedwithfunctionswarningagainstawrongdecision figure 37 To permanently delete the content of the data Bank press the F1 Yes button When the Bank data deletion is over the cur...

Страница 12: ...eryshouldbeconnectedinaccordance with the signs III Reverse connection of the battery after pause and restart of the discharge process figure 41 Ifthepauseoftheprocessoccurs bythe OFF buttonbeingpressed information about the end of the discharge process is displayed The battery can now be disconnected and connected again however its reverse connection will prevent the tester from further work Solu...

Страница 13: ... be deleted if the emergency is not resolved e g the emergency switch is on Press the F2 Cancel button to delete the emergency and then press the F1 Exit button The basic screen can be seen on the display figure 46 Press the F1 Exit button to leave the basic screen and allow for the further work of the device The battery tester is protected from power failure During the discharge process current d...

Страница 14: ...n allows you to review data from the last discharge test performed Thedataarestoredinthedevicememoryuntilthepowerisswitchedoff II Choosing the cell type figure 52 By means of the adjuster you can change the cell type Acid Alkaline If you choose Acid cells the device will assign voltage parameters of the tested cells in accordance with acid cells during the 5h 10h 20h Discharge If you choose Alkali...

Страница 15: ... should be set again To set the date and time use the F2 button and the adjuster and confirm the setting by pressing the F3 OK button c Counter settings figure 56 This function allows you to set the mode of counting time during a battery test If the parameter is set to Backwards the battery test time counts down to 0 If the parameter is set to Forwards the battery test time counts to a set value T...

Отзывы: