Operation
Page 46 of 92
User Manual QT250 and QT800 gen 2.5, ID 2021 2.3 20. April 2021
Figure 33: Manual operation of the actuator
Figure 34: Position scale
The following subsections describe what triggers an alarm, reactions from the
actuator and how the alarm is reset.
•
Trigger conditions:
One or more of the alarms POSITION UNDEFINED,
TEMPERATURE or TORQUE is active.
•
Reaction from actuator
: None for the GENERAL alarm itself, but the other
alarms that are active have reactions.
•
Reset conditions
: The alarms POSITION UNDEFINED, TEMPERATURE and
TORQUE must be inactive.
•
Trigger conditions:
The outgoing shaft of the actuator is out of range.
•
Reaction from actuator:
None besides an active alarm.
•
Reset conditions
: The outgoing shaft must be run back within range.
Valve percent position is a [0%, 100%]
value. A value of 0% corresponds to the
CLOSED position
, while a value of 100% corresponds to the
OPEN position
. Seen