22
Installation Guide
Flatpack2 -48V 150A
~ 2029242 R2, May 2008
7.
Alarm and Control Terminations
Alarm Contacts
The alarm interface board is located at the rear of the system in the distribution
section, directly behind the
Smartpack
controller. Alarm outputs are “Form-C”
contacts. There are an equal number of alarm inputs and outputs provided.
To install an alarm wire to the board:
1)
Strip the alarm wire end 3/8”.
2)
Press the white terminal clamp above the desired wire location.
3)
Insert the alarm wire, and release the terminal clamp.
The alarm connector is designed to accept a wire range of #26 AWG solid or
stranded to #18 AWG. The Form-C contacts provided in the system have a rating of
1A at 60 VDC. Please refer to the
User’s Guide—Smartpack Monitoring & Ctrl Unit
for further details of alarm relay designations and assignment procedures.
Relay Description
1
Common Alarm
2
AC Main Alarm
3
Distribution Alarm
4
High Voltage Alarm
5
Low Voltage Alarm
6
Rectifier Fail Alarm
Figure 13 - Alarm Board Terminals