Multiflow SMB

AC

SMB Inst Issue D: 27-08-13

Dimensional Data

Product 

Code

 A

B

C

D

E

Ductmate 

Flange

Impeller 

Dia.

Weight

kg

SMB350

350

400 420

9

375

25

250

22

SMB400

400

450 480

9

425

25

315

30

SMB450

450

500 470

9

475

25

350

30

SMB500

500

550 500

9

525

25

400

30

SMB550

550

620 550 11

585

35

450

44

SMB650

650

720 600 11

685

35

500

58

SMB700

700

770 650 11

735

35

560

63

SMB800

800

870 700 11

835

35

630

79

SMB1000

1000 1070 800 11 1035

35

800

147

4 HOLES     D 

2- KNOCKOUTS     21

FOR CUSTOMER 

ENTRY CHOICE

DUCTMATE FLANGE

E

B

C

AIR-FLOW

Содержание Multiflow SMB

Страница 1: ...ion and Maintenance Instructions THESE INSTRUCTIONS MUST BE READ FULLY BEFORE COMMENCING INSTALLATION SMB Inst Issue D 27 08 13 CONTENTS PAGE NO Electrical Data 2 Dimensional Data 3 Installation Instructions 4 General 4 Installation 4 Start Up 4 Fan Maintenance 4 Guarantee 4 Wiring Diagrams 5 AC ...

Страница 2: ...240V 1Ph 50Hz 2 56 0 37 1350 152 502 SMB500 4 4 2 220V to 240V 1Ph 50Hz 3 70 0 55 1350 152 502 SMB550 4 4 2 220V to 240V 1Ph 50Hz 6 28 1 0 1350 152 502 SMB650 4 4 2 220V to 240V 1Ph 50Hz 10 1 1 5 1350 152 502 Product Code Supply FLC Amps Input kW Speed r min Wiring Diagram No SMB500 6 5 3 380V to 415V 1Ph 50Hz 0 75 0 18 910 152 600 SMB500 4 5 3 380V to 415V 1Ph 50Hz 2 00 0 75 1410 152 600 SMB550 6...

Страница 3: ...ll be supplied on request Multiflow SMB AC SMB Inst Issue D 27 08 13 Dimensional Data Product Code A B C D E Ductmate Flange Impeller Dia Weight kg SMB350 350 400 420 9 375 25 250 22 SMB400 400 450 480 9 425 25 315 30 SMB450 450 500 470 9 475 25 350 30 SMB500 500 550 500 9 525 25 400 30 SMB550 550 620 550 11 585 35 450 44 SMB650 650 720 600 11 685 35 500 58 SMB700 700 770 650 11 735 35 560 63 SMB8...

Страница 4: ...n must be isolated from the power supply during installation and maintenance The fan must be earthed in accordance with the local regulations 2 1 Upon receipt the fan equipment should be visually inspected to check for any damage Ensure that the impeller is free to rotate 2 2 If there are any queries concerning the fan equipment Elta Fans Ltd should be contacted prior to the installation 2 3 The f...

Страница 5: ...Hz SUPPLY FIXED SPEED CONNECTION GREEN YELLOW BLUE BROWN E L N N L AUX VARIABLE SPEED CONNECTION CONTROLLER TYPE EL31 EL61 EL101 BROWN BROWN BLUE GREEN YELLOW CONTROLLER TERMINAL BOX E L N GREEN YELLOW BROWN BLUE REMOVE LINK BETWEEN U1 Z2 Z2 U1 Z1 U2 CAP1 CAP2 220 240V 1PH 50Hz SUPPLY BROWN BROWN BLUE GREEN YELLOW E L N CONTROLLER TERMINAL BOX GREEN YELLOW BROWN BLUE VARIABLE SPEED CONNECTION CONT...

Страница 6: ...TER ANALOG DIGITAL INPUT CONNECTIONS 3PH 3PH IP20 INVERTER 10 RELAY COMMON 11 RELAY CONTACT L2 380 440V 3PH 50Hz SUPPLY FAN TERMINAL BOX L1 E 1 24V OUTPUT 2 STOP RUN DI1 3 FWD REV DI2 4 ANALOG PRESET DI3 5 10V OUTPUT 6 ANALOG INPUT 7 0V GREEN YELLOW GREY BLACK BROWN GREEN YELLOW GREY BLACK BROWN L2 E L3 L1 380 440V 3PH 50Hz SUPPLY FIXED SPEED Y CONNECTION W2 U2 V2 U1 W1 V1 FAN TERMINAL BOX GREEN Y...

Страница 7: ...TPUT 6 ANALOG INPUT 7 0V GREEN YELLOW GREY BLACK BROWN W2 U2 V2 U1 W1 V1 GREEN YELLOW GREY BLACK BROWN BROWN BLACK GREY GREEN YELLOW FAN TERMINAL BOX L2 E L3 L1 380 440V 3PH 50Hz SUPPLY FIXED SPEED Δ CONNECTION W2 U2 V2 U1 W1 V1 1 TO 7 PRE WIRED 10 RELAY COMMON 11 RELAY CONTACT L3 ANALOG DIGITAL INPUT CONNECTIONS 3PH 3PH IP55 INVERTER L2 380 440V 3PH 50Hz SUPPLY FAN TERMINAL BOX L1 E GREEN YELLOW ...

Страница 8: ...SCP SCPA SCD SCPP SPP SLC SAMF SMB SMC SMT SCC HIT SJS SH SSD SQS SQSDCV STD SQT SQTDCV SPD SQU SQU HT SSQU SSR SSF SSMF SMF SSDR SSDRDCV STDR STDRDCV SGE SCH SCHT SSFV SSRV SSC SB SDF HCF SEIE SEWE The design of the partly completed machines listed below complies with the Essential Health and Safety Requirements EHSRs of ANNEX I sections 1 1 2 1 1 5 1 4 1 1 5 1 in EC Machinery Directive 2006 42 E...

Страница 9: ...g Estate Kingswinford West Midlands DY6 7US United Kingdom APPLIED TECHNOLOGY Tel 44 0 1489 566500 Fax 44 0 1489 566555 e mail at eltafans co uk 17 Barnes Wallis Road Segensworth East Industrial Estate Fareham Hampshire PO15 5ST United Kingdom EXPORT Tel 44 0 1489 566500 Fax 44 0 1489 566555 e mail export eltafans co uk 17 Barnes Wallis Road Segensworth East Industrial Estate Fareham Hampshire PO1...

Отзывы: