2

AC

VERSALINE VL

Installation Instructions

1.    

WARNING 

- This fan is fitted with a non self-resetting thermal cut-out which switches the fan off in the event of a fault condition. To reset,  

 

 

turn the power off for one minute, then back on. Only a suitably qualified and competent person may carry out maintenance after the    

 

 

electrical supply has been isolated.

   CAUTION 

-

 

In order to avoid a hazard due to inadvertent resetting of the thermal cut-out, this appliance must not be supplied through an  

 

 

external switching device, such as a timer, or connected to a circuit that is regularly switched on and off by the utility.

   WARNING 

-

 

The appliance can only be used indoors.

2.0   

General 

2.1    

It is important these Installation and Maintenance Instructions are fully adhered to.

2.2    

Full details of the unit supplied are shown on the product nameplate. If in doubt about any detail contact Elta Fans or its agents 

 

 

for clarification.

2.3    

All electrical installation must be carried out by suitably qualified and competent personnel in accordance with all current statutory  

 

 

requirements.

2.4    

These instructions cover only the Elta Fans Ltd product and do not include the supply or installation of any safety equipment that may  

 

 

be required e.g. adequate guarding or protection from rotating parts and proper electrical isolation.

2.5    

Any declarations made by Elta Fans Ltd about product installation and safety, are dependent on the fan equipment being used within  

 

 

installations which themselves meet the requirements of the relevant Standards and Directives of your region.

2.6    

The fan is designed for use in up to 95% relative humidity. The fan is not suitable for corrosive or explosive atmospheres.

2.7    

The installer should provide easy access to the fan to facilitate future maintenance.

2.8    

The installer should ensure the fan is adequately supported.

2.9    

The below statement is only applicable to the European market.

 

 

 

This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental  

 

 

 

capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance  

 

 

in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall    

 

 

not be made by children without supervision.

2.10   

The below statement is only applicable to the non-European market.

 

 

 

This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of  

 

 

experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person  

 

 

responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.

2.11  

Means for electrical disconnection must be incorporated in the wiring installation in accordance with the relevant wiring and electrical  

   regulations.

 
  

WARNING 

-The fan must be isolated from the power supply during installation and maintenance. The fan must be earthed in accordance  

 

 

with the local regulations. The appliance can only be used indoors.

3.0

3.1   

Refer to the appropriate wiring diagram. Ensure that all earth connections are made.

3.2   

The fan is to be installed so that the blades are more than 2.3m above the floor (for fans intended to be mounted at high level).

3.3   

Precaution must be taken to locate the exhaust discharge terminal so as to avoid the backflow of gases into the room from the open  

 

 

flue of gas or other fuel burning appliances.

  

Owner / installer:

 The life of this apparatus and its efficiency will be increased if its use and maintenance is carried out in accordance  

 

 

with these instructions and current statutory requirements. The installation and initial adjustments should be carried out by a  

 

 

qualified and competent technician. Elta Fans Limited should be consulted before substituting or fitting parts from another  

 

 

manufacturer. It is the responsibility of the installer to verify that the installation is in accordance with the following standards and the  

 

 

owner is given the current User’s Manual.

  

Any modifications to the fan or its installation, even the smallest modification, change or elimination of security  

 

 

components or pieces that influence the efficiency or loss of ventilation, will result in Elta Fans’ warranty 

 

 

being cancelled.

4.    

Installation 

4.1    

Upon receipt, the fan equipment should be visually inspected to check for any damage. Ensure that the impeller is free to rotate. 

4.2   

If there are any queries concerning the fan equipment, Elta Fans should be contacted prior to the installation. 

4.3   

Use the mounting bracket set supplied with the VL fan to fix the fan in the desired position to suit the application. The fan can be  

 

 

mounted at any angle. If the fan is mounted with vertical outlet, a weather proof cover must be installed at the ducted outlet.

Содержание VERSALINE VL

Страница 1: ...These instructions must be read fully before commencing installation VERSALINE VL Installation Maintenance...

Страница 2: ...ade by children without supervision 2 10 The below statement is only applicable to the non European market This appliance is not intended for use by persons including children with reduced physical se...

Страница 3: ...button head screws Mounting bracket set supplied VL100 VL125 and VL150 2 off bracket sides Fixings set supplied a 4 off M4x8mm Phillips hexagon with pad flange head self tapping screws a Bracket side...

Страница 4: ...t the cable is securely clamped and cannot move Tool requirments not supplied 24mm Spanner Terminal screw driver 4 8 If the supply cord is damaged it must be replaced by the manufacturer its service a...

Страница 5: ...t 5 AC VERSALINE VL Installation Instructions Code Article No Supply FL Amps Watts r min VL100 008000 220 240V 1Ph 50 60Hz 0 14 0 13 26 25 2725 3150 VL125 008001 220 240V 1Ph 50 60Hz 0 14 0 12 26 25 2...

Страница 6: ...98 204 130 237 284 270 47 3 7 VL125 123 202 130 237 284 270 47 3 7 VL150 148 195 165 278 326 312 47 3 6 VL200 198 242 190 333 392 372 100 5 5 VL250 248 210 190 333 392 372 100 5 3 VL315 313 280 227 4...

Страница 7: ...red with flying lead and UK 3 pin plug where connection to control devices all units or change of operating speed Units 150 315 refer to diagrams below 8 1 VL100 125 8 2 VL150 315 152 001 Wiring Diagr...

Страница 8: ...o uk 46 Third Avenue Pensnett Trading Estate Kingswinford West Midlands DY6 7US United Kingdom Hydor and Elta fans are Companies and brands wholly owned by the Elta Group Limited BS EN ISO 9001 2015 F...

Отзывы: