Part 2: Overview of display values and settings
Expert
area
27
Screed program
Screed
Designation Value
range
Standard
Screed Off/On Off
Screed Program
See explanation!
Use the F button [End] to exit the level
Preset values
Day T-Flow
Own
settings
1 25
2 25
3 25
4 55
5 55
6 55
7 55
8 25
9 40
10 55
11 55
12 55
13 55
14 55
15 55
16 55
17 55
18 55
19 55
20 40
21 25
23 --
24 --
25 --
26 --
27 --
28 --
!
Start day is not included:
The screed program starts with the "Day 1"
temperature setting and switches to "Day 1" at
00.00 hrs and then to the next day at 00:00 hrs and
so on. The current day is marked with an "x" in the
"Screed Program”.
!
After the function has been cancelled/terminated
the controller continues heating using the set
operating mode. If no heating is required, set the
operating mode to
i
= Standby / OFF.
Screed
(activation of screed drying process)
The screed program can be used for function heating in
accordance with DIN EN 1264–4 and for heating freshly
laid screed ready for flooring.
!
Screed drying can only be carried out for mixer
circuits.
After starting, the program runs through the set flow
temperatures. The integrated mixer circuits control to the
set flow temperature. The boiler provides this
temperature irrespective of the operating mode that has
been selected. This is marked in the standard display by
the entry "SCREED" and a display of the current flow
temperature.
The freely adjustable program runs for a maximum of
28 days. The flow temperatures can be set to a value of
between 10°C and 60°C for each day. The entry "----"
stops the program (also during operation for the following
day).
Screed Program
(settings)
F button => Screed Program
Select day => Temperature is displayed
F button [OK] => Activate the day for the adjustment
Set the flow temperature;
F button [OK] => Save setting
=> Select Next Day or exit the screed program using
the F button [End].