Elster EnergyAxis Gatekeeper 2210 Скачать руководство пользователя страница 5

EA_Gatekeeper model 2210 Ethernet backhaul

5

Remote external antennas: PCTEL/MAXRAD P/N MFB9380 (Tessco P/N 61900) for unity gain (2.15 dBi);
PCTEL/ MAXRAD P/N MFB 9153 (Tessco P/N 74300) for 3 dB gain (5.15 dBi)

There are several options for remote antenna cabling. The most economical connection to the external
remote antenna is the LMR-400 type cable. This type of cable is suitable for distances up to 100 feet
(approximately 30 meters). Antenna cables should be ordered with the N-type male connectors on
each end. One end attaches to the gatekeeper housing, and the other end attaches to the antenna.
You can perform on-site assembly or order pre-assembled cables (for example, from Laird
Technologies).

WAN communications

The EA_Gatekeeper model 2210 is equipped with an Ethernet communications option board. This
option board is connected to an internal Ethernet surge suppressor. The external Ethernet device cable
is routed through the Ethernet cable gland and connected into the bottom of the Ethernet surge
suppressor. The cable used must be rated for outdoor use, have a minimum CAT 5 rating, and have
EMI/RFI shielding with conductive RJ-45 connectors. The cable shielding is connected to ground on the
EA_Gatekeeper side and should be left ungrounded on the external equipment side to prevent a
ground loop scenario.

Placing the EA_Gatekeeper model 2210 into service

Use authorized utility procedures when installing the EA_Gatekeeper model 2210. Dangerous
voltages are present. Equipment damage, personal injury, or death can result if authorized utility
procedures are not followed when installing the EA_Gatekeeper.

The EA_Gatekeeper model 2210 is a FCC Part 15 Class A device, and it is not intended for installation in
or on a residence. See the FCC Part 15 Class A compliance statement on page 9.

Be sure to properly ground the EA_Gatekeeper before placing the gatekeeper into service.

Содержание EnergyAxis Gatekeeper 2210

Страница 1: ...keeper can be enclosure mounted in different form factors This leaflet explains how to install the gatekeeper model 2210 This model of EA_Gatekeeper is configured for 120 VAC to 277 VAC nominal operation and uses a battery backup for gatekeeper operation if AC power fails at the site The EA_Gatekeeper model 2210 uses a NEMA 4X rated polycarbonate enclosure The gatekeeper supports different mountin...

Страница 2: ...er supply Pb battery charger 6 7 Heater power terminals 8 Heater fuse 9 Thermostat 10 AC power fuses 11 Surge protective device 12 Heater 13 LAN RF filter 14 Enclosure latches lockable 15 Metal enclosure vent 16 3rd party WAN antenna hole plugs 17 Universal mounting bracket 18 LAN antenna Must be field configured May be bulkhead for remote antenna 19 PE ground lug 20 AC cable entry gland 19 19 18 ...

Страница 3: ...lass A compliance statement on page 9 For optimal performance of the LAN antenna Honeywell recommends that the EA_Gatekeeper model 2210 be installed so that the enclosure is at least 5 feet 1 5 meters off the ground Failure to meet the minimum ground clearance can result in degraded performance of the EA_Gatekeeper model 2210 communication within the EnergyAxis or Connexo systems The EA_Gatekeeper...

Страница 4: ...ratures are below freezing first gently warm the enclosure around the lid gasket to ensure the gasket is not frozen to the sealing surface LAN communications The gatekeeper supports different antenna options If the antenna is mounted on the unit itself that is a local external antenna no additional steps are required when placing the gatekeeper into service If the gatekeeper is to be installed at ...

Страница 5: ...ernal Ethernet surge suppressor The external Ethernet device cable is routed through the Ethernet cable gland and connected into the bottom of the Ethernet surge suppressor The cable used must be rated for outdoor use have a minimum CAT 5 rating and have EMI RFI shielding with conductive RJ 45 connectors The cable shielding is connected to ground on the EA_Gatekeeper side and should be left ungrou...

Страница 6: ...ction instructions 120 VAC Figure 3 Connect heater wire 23 to thermostat flag terminal D Using jumper Z connect heater wire 22 and 24 to DIN rail position B Torque the DIN rail terminal screw to 5 inch pounds 0 565 Newton meters 240 277 VAC Figure 4 Heater wire 22 connects to thermostat flag terminal D Heater wire 23 connects to DIN rail terminal C Use jumper Y to make this connection Torque the D...

Страница 7: ...he enclosure 5 If you are using a remote antenna option mount the external antenna and route the cable through the lightning arrestor bulkhead 18 Use coax sealant to waterproof these connections 6 Apply AC power as appropriate for the intended AC power operation Power is applied to the gatekeeper by a cable that enters the enclosure through the base of the unit 20 and connects to the AC line SPD 1...

Страница 8: ...m battery power Off Normal operation AC power is present at the DC power supply battery charger Low battery or battery replacement On With AC power absent this indicates the operational backup battery 3 is critically low and on the verge of failure With AC power present the battery fuse might be faulty or the battery requires service Off Normal operation Battery is within normal parameters and con...

Страница 9: ...nnas located within 20 cm of each other within a final product is not allowed Trademark notices EnergyAxis is a trademark and or registered trademark of Elster Other names may be trademarks and or registered trademarks of their respective owners FCC and Industry Canada Compliance User Information Part 15 105 This equipment has been tested and found to comply with the limits for a Class B digital d...

Страница 10: ...covering all contingencies If further information is required Elster Solutions LLC should be consulted No warranties either expressed or implied including warranties of fitness for a particular purpose or merchantability or warranties arising from the course of dealing or usage of trade are made regarding the information recommendations descriptions warnings and cautions contained herein In no eve...

Отзывы: