AirHeat, V1, Operating Instructions, Edition 09.12
Ignition
Ignition voltage should be 6000 VAC.
Approval of Components
Limit Controls & Safety Equipment
All limit controls and safety equipment must comply with
all applicable local codes and/or standards and must be
listed for combustion safety by an independent testing
agency. Typical application examples include:
• American: NFPA 86 with listing marks from UL, FM,
CSA
• European: EN 746-2 with CE mark from TuV,
Gastec, Advantica
Electrical Wiring
All the electrical wiring must comply with all applicable
local codes and/or standards such as:
• NFPA Standard 70
• IEC60364
• CSA C22
• BS7671
Gas Piping
All the gas piping must comply with all applicable local
codes and/or standards such as:
• NFPA Standard 54
• ANSI Z223
• EN 746-2
Where to Get the Standards:
The NFPA Standards are available from:
National Fire Protection Agency
Batterymarch Park
Quincy, MA 02269
www.nfpa.org
The ANSI Standards are available from:
American National Standard Institute
1430 Broadway
New York, NY 10018
www.ansi.org
Duct Design and Burner Mounting
Duct Design
See Figure 3 for typical mounting arrangements and duct
designs.
Support
The mounting flange or brackets supplied with an AH
burner are capable of supporting the weight of the burner
and blower. The AH burner case itself is designed to
support the weight of the blower, so the blower does not
require independent support.
Valve Train Support
Support valve trains independently of the burner.
Gas Piping
Use flexible nipples to allow for thermal expansion of the
burner.
Check Valve Piping
Gas flow through the check valve must be horizontal. See
Figure 1.