10 .4 Behaviour during operation
10 .4 .1 Restart
Parameter 09
This parameter determines whether the BCU initiates an im-
mediate safety shut-down with fault lock-out or an automatic
restart after a flame failure during operation. Excessive restarts
(max. 5) can also be detected.
In accordance with EN 746-2, a restart may be conducted
only if the safety of the installation is not impaired. A restart is
recommended for burners which occasionally display unstable
behaviour during operation.
The precondition for an automatic restart is that the burner
can restart (as intended in all operating phases). In this case,
it must be ensured that the program sequence started by the
BCU matches the application.
Parameter 09 = 0: Off.
04
t
t
SB
04
88
ϑ
1
46
11
9
5
13
V1
57
V4
L1
42
41
A safety shut-down with subsequent fault lock-out takes place
in the event of flame failure during operation.
Parameter 09 = 1: burner 1. The restart function is active.
t
SA
t
Z
04
04
02
03
01
t
t
FS
t
W
t
SB
1x
>2 s
88
ϑ
1
46
9
5
13
V1
57
V4
11
L1
42
41
If a flame failure occurs during operation (minimum operating
time of 2 s), the valves are closed and the operation signalling
contact is opened within the safety time during operation t
SB
.
The burner control unit then attempts to restart the burner
once. If the burner does not function, a safety shut-down with
fault lock-out occurs. The display blinks and shows the fault
message.