16 TECHNICAL
DATA
Current: Standard Range (Direct connected)
Extended Range (Direct connected)
Standard Range (CT operated)
Extended Range (CT operated)
20 - 100A (BS), 10 – 60A (DIN)
5 - 100A (BS), 5 – 85A (DIN)
5 - 10A
1 - 2A
Frequency
Reference Voltages
Voltage Operating Range
System Connection - 2 element meter
- 3 element meter
50 Hz
220-230-240V (3ph, 4wire), 220-230-240 (3ph-3wire)
+/- 20%
3 phase 3 wire
3 phase 4 wire
2 phases of a 3 phase 4 wire
2 phase 3 wire
1 phase 3 wire
1 phase 2 wire (LCD meter only)
Starting Current
Short Circuit Current
Burden of Voltage Circuits 230V
Burden of Current Circuits (10 – 100A meter)
Dielectric Strength
Impulse Withstand
0.004Ib (Class 1), 0.005Ib (Class 2)
30 Imax
0.9W, 9VA capacitive burden per phase [max]
2VA at 100A per phase [max]
4kV RMS
12kV 1.2/50
μ
s 50 ohm source
Display
Stepper Register
LCD 9.8 x 3.5mm characters, high contrast, wide viewing angle
7 digits, each 6.7mm x 3.5mm. 1/10 or 1/100 kWh resolution
Meter Constant (pulsing LED output)
500 p/kWh (Direct Connected)
5000p/kWh (CT Operated)
Pulse Output Specification
Max Rating
Pulse Width/value (Default)
IEC 62053-31 (Transistor Output)
27V d.c. 27 mA
100 ms pulse 500p/kWh (= 5Wh/pulse)
Product Life
Certified Life
16 years
10 years
Temperature
Humidity
Operational range: -40
°
C to +55
°
C
Limit Range: -40
°
C to +65
°
C
Storage Range: -40
°
C to +85
°
C
Annual Mean 75% (95% for 30 days spread over one year)
Dimensions
Weight
221mm (High) x 174 mm (Wide) x 50mm (Deep)
904 grams (LCD Meter) 943 grams (Stepper Meter)
Accuracy Class kWh
Class 1 or Class 2 - EN 61036:1996 (plus amendment 1:2000)
Case
DIN 43857 Part 2 and Part 4 (except for top fixing centre)
IP53 to IEC 60529:1989
EMC Directive 89/336/EEC
Terminals Main
Auxiliary
Auxiliary Voltage
8.2mm bores, M6 Terminal Screws – max torque 3.0 N m
3.2 mm bores, M3 Terminal Screws – max torque 0.45 N m
3.2 mm bores, M3 Terminal Screws – max torque 0.45 N m
Note 1
The contrast of the LCD may be impaired at temperatures lower than -20
°
C. This will not
however damage the display and the contrast will return to normal when the temperature rises above
-20
°
C.
Содержание A1100