Function Expansion Unit FE260
Elster-Instromet GmbH
13
3.3.2 Terminal layout
With an EK260 volume corrector, set “TypS2” = “2” before you connect it to the
FE260 in order to avoid damage to the devices.
Cable 1
White
+
+
Brown
FE260
U
-
-
Uext
Volume corrector
e.g.
EK260
Green
+
+
Yellow
R
-
-
R
Grey
+
+
Pink
T
-
-
T
Blue
+
+
Red
„DC“ version
only
DE3
-
-
DE3
White
+
+
Brown
DA1
-
-
DA1
Green
+
+
Yellow
DA2
-
-
DA2
Grey
+
+
Pink
DA3
-
-
DA3
Blue
+
+
Red
DA4
-
-
DA4
if present
Cable 2
On the EK260 the terminals “R+”, “R-“, “T+” and “T-“ are also labelled with “CS”, “RD”,
“RS” and “TD”. When connecting the FE260, these designations have no significance. The
terminals “Ri” and “Gnd” on the EK260 remain unconnected.
The cable designations (Cable 1 and Cable 2) and the suggested core colours are based
on the use of two similar cables, LiYCY 4 x 2 x 0.5 mm², twin-twisted with colour code
according to DIN 47100. Suitable cables can also be obtained from Elster-Instromet (see
II-2, Options).
With "AC" versions (with 230V or 115V power supply) the blue and red wires of Cable 1
remained unused. They should then be cut off at both ends flush with the cable sheath or
safely insulated to prevent hazardous short circuits from forming.
Of course, other cables can also be used provided they conform to the requirements
quoted in 0. Similarly, a different designation of the core colours is possible.
Содержание 83 480 540
Страница 25: ...Function Expansion Unit FE260 Elster Instromet GmbH 25 A Approvals A 1 EC Declaration of Conformance ...
Страница 26: ...Function Expansion Unit FE260 26 Elster Instromet GmbH A 2 Approval as associated operating equipment ...
Страница 27: ...Function Expansion Unit FE260 Elster Instromet GmbH 27 ...
Страница 28: ...Function Expansion Unit FE260 28 Elster Instromet GmbH ...
Страница 29: ...Function Expansion Unit FE260 Elster Instromet GmbH 29 ...