AHU Resistors Humidifier - REH
21.2.EN
6
Elsteam S.r.l - via E. Fermi, 496 - 21042 Caronno Pertusella (va) - Tel.+39 02 9659890 - Fax +39 02 96457007
E-mail: [email protected] Web: http://www.elsteam.com
Models
REH4
REH12
REH24
REH36
REH48
PRODUCTION
Steam Capacity
[Kg/h]
4
12
24
36
48
Max Pressure
[mm H2O/bar]
no limits under normal conditions within the AHU
ELECTRICAL DATA
Power
[kW]
3
9
18
27
36
Supply
[Vac, Hz]
230, 50
400, 50
Phases
[n]
1
3
Max Current per Phase
[A]
13
13
26
39
52
HIDRAULIC DATA
Input Water Quality
Complies with the microbiological requirements defined for drinking water by
the regulations in force in the area of use; the use of totally or partially demin-
eralized water is recommended to reduce the frequency of maintenance
Input Water Conductibility
μS*cm
0...1250
Input Water Hardness
°Fr
0...50
Input Water Pressure
[MPa/bar]
0,02...1/0,2...10
Input Water Connection
M 3/4” G
Drain Water Connection
[mm]
42
GENERAL DATA
Control Unit Dimensions
(HxWxD [mm])
350x400x150
Hydraulic Unit Dimensions
(HxWxD [mm])
150x250x950
150x250x950
150x280x950
150x365x950
150x520x950
Weight
[kg]
18
23
28
33
41
IP Hydraulic Unit
20
IP Control Unit
44
REGULATION
Control
Controllore Interno (sonda umidità 4-20mA), segnale esterno (0-10V, ON-OFF)