AHU Resistors Humidifier - REH
21.2.EN
12
Elsteam S.r.l - via E. Fermi, 496 - 21042 Caronno Pertusella (va) - Tel.+39 02 9659890 - Fax +39 02 96457007
E-mail: [email protected] Web: http://www.elsteam.com
10
Alarms
DISPLAY
Description
Resolution
A L A R M
NTC KO
NTC open
Damaged element or low temperature
Check NTC element
Check heater connections
Check contactors
A L A R M
RESISTOR T.
Heater element temperature above 125°C
The humidifier stops for some minute to lower tempera-
ture, and then restarts, so to avoid damaging of heaters
A L A R M
LACK WATER
No water in the kettle
Check the input solenoid
Check the electrical connections of the solenoid
A L A R M
DRAIN MOTOR
The drain motor is not closed within the al-
lotted time. (Timeout of closing)
Check the electrical connections of the motor
Check that there are no blocks of limestone or objects
blocking the closure
A L A R M
CLOGGED DRAIN
limestone blocks draining block
Check the amount of scale in the kettle/draining block.
Perform manual cleaning of kettle/draining block