Product Manual, Issue 6
CMS200
www.nexo.com
Page 52
6.3.18 Buzzer duration (b1)
Display
Description
Defines the duration of the buzzer for door open alarm conditions.
If the door remains open after the buzzer duration (b1), the controller switches off the
compressor for the duration of RT before starting door open ‘limp home’ mode.
Considerations
The controller switches off the compressor after the duration defined by alarm delay
(Ad) + buzzer duration (b1 ).
Range
1 to 254 seconds
Global default
60 seconds
6.3.19 Motion sensor enable (Sn)
Display
Description
Enables the input from the motion sensor.
Considerations
Must be disabled if a motion sensor is not fitted.
Range
0 (disabled) or 1 (enabled)
Global default
1 (enabled)
6.3.20 Display stability (d2)
Display
Description
Defines the rate of change of the displayed temperature.
Limiting the rate of change provides a dampening effect so as not to concern users
should the air temperature rise quickly due to a door opening.
Increasing the value for the display stability (d2) slows the rate of change of the
displayed temperature.
Considerations
Use the global default value for normal operation.
Range
1 to 254
Global default
46