24
Parameter setting
Sensor KNX T-UP gl
• Version: 05.09.2022 • Technical changes and errors excepted.
Enter the hysteresis that prevents frequent on/off switching of temperatures in the
threshold range.
If separate control variables are used, select whether the control variable of the 2nd
level is a 1 bit object (on/off) or an 8 bit object (on with percentage/off).
Now specify what should be sent when the control is blocked.
On release, the control variable follows the rule again.
In case of a common control variable for heating and cooling, 0 is always transmitted
as a fixed value.
5.6.
Variable comparator
The two integrated control variable comparators can output maximum, minimum and
median values.
5.6.1. Control variable comparator 1/2
Determine what the control variable comparator should output, and activate the input
objects to be used. Send behaviour and blocks can also be set.
Control type
is determined at a higher level for common
variables
•
2-point-control
Hysteresis (in 0.1°C)
0...100; 20
Control variable is a
• 1 bit object
• 8 bit object
Value (in %)
(for 8 bit object)
0...100
When blocked, the control variable shall
• not be sent
• send a specific value
Value (in %)
(if a value is sent)
0...100
Use comparator 1/2
No • Yes
Output delivered
• Maximum value
• Minimum value
• Average value
Use input 1/2/3/4/5
No • Yes
Output sends
• on change of output
• on change of output and periodically
• when receiving an input object
• when receiving an input object and peri-
odically
From change of
(is only sent if "on change" is selected)
1% • 2% • 5% • 10% • 20% • 25%