19
Parameter setting
Sensor KNX T-UP gl
• Version: 05.09.2022 • Technical changes and errors excepted.
If setpoint values are entered separately:
A starting setpoint value is defined as well as a temperature range in which the setpoint
value may be changed.
If the comfort setpoint value is used as a basis:
If the comfort setpoint value is used as a basis, the reduction/increment of the value is
set.
Setpoint values for frost/heat protection (building protection)
The building protection mode is for example used as long as windows are opened for
ventilation. Setpoints for frost protection (heating) and heat protection (cooling) are
determined which may not be modified from outside (no access via operating devices
etc.). The building protection mode may be activated with delay, which allows you to
leave the building before the controls switch to frost/heat protection mode.
General control variables
This setting appears for the control types "Heating
and
Cooling" only. Here, you can
decide whether to use a common control variable for heating and cooling. If the 2nd
level has a common control variable, you also determine the control mode of the 2nd
level here.
Starting heating setpoint (in 0.1 °C)
valid until 1st communication
-300…800; 160
Starting cooling setpoint (in 0.1 °C)
valid until 1st communication
-300…800; 280
Min. object value heating/cooling
(in 0.1 °C)
-300…800; 160
-300…800; 280
Max. object value heating/cooling
(in 0.1 °C)
Reduce heating setpoint (in 0.1°C)
(for heating)
0…200; 50
Increase cooling setpoint (in 0.1°C)
(for cooling)
0…200; 60
Setpoint frost protection (in 0.1°C)
-300…800; 70
Activation delay
less than • 5 s • ... • 5 min • … • 2 h
Setpoint heat protection (in 0.1°C)
-300…800; 350
Activation delay
none • 5 s • ... • 5 min • … • 2 h
For heating and cooling
• separate control variables are used
• common control variables are used for
Level 1
• common control variables are used for
Level 2
• common control variable are used for
Level 1+2