Transfer protocol

Weather Station Suntracer KNX sl basic

 • Version: 11.03.2016 • Technical changes and errors excepted.

5.

Transfer protocol

Units:

Temperatures in degrees Celsius
Brightness in Lux
Wind in metres per second
Air pressure in Pascal
Azimuth and elevation in degrees

5.1.

List of all communications objects

Abbreviation flags:

C

Communication

R

Read

W Write
T

Transmit

U

Update

No.

Text

Function Flags

DPT type

Size

1

Software version

Output

R-CT

[217.1] DPT_Version

2 bytes

21

Signal LED object 1s cycle

Input

-WC-

[1.1] DPT_Switch

1 bit

22

Signal LED object 4s cycle

Input

-WC-

[1.1] DPT_Switch

1 bit

34

Rain: Switching output

Output

R-CT

[1.1] DPT_Switch

1 bit

35

Rain: Switching output with fixed 
delays

Output

R-CT

[1.1] DPT_Switch

1 bit

36

Rain: Switching delay to rain

Input

-WC-

[7,005] DPT_TimePeri-
odSec

2 bytes

37

Rain: Switching delay to no rain

Input

-WC-

[7,005] DPT_TimePeri-
odSec

2 bytes

41

Temperature sensor: Malfunction

Output

R-CT

[1.1] DPT_Switch

1 bit

42

Temperature sensor: External meas-
urement

Input

-SKÜ

[9.1] DPT_Value_Temp 2 bytes

43

Temperature sensor: Measurement 
value

Output

R-CT

[9.1] DPT_Value_Temp 2 bytes

44

Temperature sensor: Total measure-
ment

Output

R-CT

[9.1] DPT_Value_Temp 2 bytes

45

Temperature sensor: Min./Max. meas-
urement query

Input

-WC-

[1.017] DPT_Trigger

1 bit

46

Temperature sensor: Minimum meas-
urement

Output

R-CT

[9.1] DPT_Value_Temp 2 bytes

47

Temperature sensor: Maximum meas-
urement

Output

R-CT

[9.1] DPT_Value_Temp 2 bytes

48

Temperature sensor: Min./Max. meas-
urement reset

Input

-WC-

[1.017] DPT_Trigger

1 bit

51

Temp. threshold value 1: Absolute 
value

Input/
Output

RWCT [9.1] DPT_Value_Temp 2 bytes

52

Temp. threshold value 1: (1:+ | 0:-)

Input

-WC-

[1.1] DPT_Switch

1 bit

Содержание Suntracer KNX sl basic

Страница 1: ...r Station Item number 70156 Elsner Elektronik GmbH Control and AutomationTechnology Sohlengrund 16 75395 Ostelsheim Phone 49 0 7033 30945 0 info elsner elektronik de Germany Fax 49 0 7033 30945 20 www elsner elektronik de Technical support 49 0 70 33 30 945 250 ...

Страница 2: ... all communications objects 15 6 Parameter setting 32 6 0 1 Behaviour on power failure power restoration 32 6 0 2 Storage of threshold values 32 6 0 3 Malfunction objects 32 6 1 Rain 32 6 2 Temperature measurement value 33 6 3 Temperature threshold values 34 6 3 1 Temperature threshold value 1 4 34 6 4 Frost alarm 36 6 5 Brightness measurement value 37 6 6 Brightness threshold values sensor 1 3 an...

Страница 3: ...ohlengrund 16 75395 Ostelsheim Germany Weather Station Suntracer KNX sl basic from software version 1 00 ETS programme version 1 0 Status 11 03 2016 Errors excepted Subject to technical changes 6 14 3 Connection inputs of the OR logic 59 ...

Страница 4: ...leshooting of the device must only be carried out by a competent electrician Safety advice Safety advice for working on electrical connections components etc DANGER indicates an immediately hazardous situation which will lead to death or severe injuries if it is not avoided WARNING indicates a potentially hazardous situation which may lead to death or severe injuries if it is not avoided CAUTION i...

Страница 5: ...itation detection The sensor surface is heated so that only drops and flakes are recognised as precipitation but not mist or dew When the rain or snow stops the sensor is soon dry again and the precipitation warning ends Temperature measurement Frost protection for shading systems Switching outputs for all measured and computed values Threshold values can be adjusted per parameter or via communica...

Страница 6: ...at 12V DC max 185 mA at 24V DC max 90 mA at 24V AC max 82 mA Bus current max 10 mA Data output KNX BCU type Integrated microcontroller PEI type 0 Group addresses max 2000 Assignments max 2000 Communication objects 341 Temperature sensor Measurement range 30 C 50 C Resolution 0 1 C Accuracy 0 5 C at 30 C 25 C 1 5 C at 30 C 45 C Wind sensor Measurement range 0 m s 35 m s Resolution 0 1 m s Accuracy ...

Страница 7: ...rt inform the supplier immediately The device may only be used as a fixed site installation that means only when assem bled and after conclusion of all installation and operational start up tasks and only in the surroundings designated for it Elsner Elektronik is not liable for any changes in norms and standards which may occur after publication of these operating instructions 2 2 Installation loc...

Страница 8: ... Temperature variations from such sources of interference must be corrected in the ETS in order to ensure the specified accuracy of the sensor temperature offset Abb 1 There must be at least 60 cm clearance to other elements structures construction parts etc below to the sides and in front of the weather station 60 cm Abb 2 The weather station must be attached to a vertical wall or a pole wall or ...

Страница 9: ... to be shaded Abb 5 1 Programming LED 2a b c Brightness measurement 3 Precipitation sensor in lid 4 Temperature measurement 5 Wind measurement 6 Programming key on the underside of the housing recessed see Addressing the equipment page 13 ATTENTION Sensitive wind sensor Remove the protective transport sticker after installation Do not touch the sensor on the wind measuring element no 5 4 5 1 2a 3 ...

Страница 10: ...semble the lower part of the housing with the integrated mounting for wall or pole installation Wall installation Use fixing materials dowels screws that are suitable for the base Abb 6 Slacken both screws on the lid top and lo wer part bottom with a size 6 Torx screwdri ver Abb 7 Pull the lid and lower part completely apart This also releases the plug in connection bet ween the board in the lid a...

Страница 11: ...plan is included ex works and this can be used as a tem plate Abb 9 a b a If the power lead is to be hidden when in stalled it must emerge from the wall in the vicinity of the rear of the housing marked area b If the power lead is to be surface moun ted the cable guide is broken off The lead is then fed into the device at the un derside of the housing Cable guide Abb 10 Feed the power lead through...

Страница 12: ...nection The connector is in the lower part of the housing Abb 11 Dimensions in mm Variations are possible for technical reasons A B2 longitudinal holes 8 mm 5 5 mm C Position of the cable outlet rub ber gasket in the housing A B C Abb 12 Feed the mounting band through the eyelets in the lower part of the housing Abb 13 Break the cable guide off Feed the power lead through the rubber gas ket Cable ...

Страница 13: ... value and thus also all wind switching outputs cannot be out put until 35 seconds after the power is turned on Abb 14 Connect KNX data and power supply 12 40V DC 12 28V AC 1 2 to the connector The terminal assignment of the power supply is polarity independent 1 2 1 2 KNX Voltage Abb 15 Push the lid on the lower part This also ma kes the plug in connection between the board in the lid and the soc...

Страница 14: ...dress 15 15 250 or teach the device using the programming button The programming button can be reached through the opening on the underside of the housing it is recessed by approx 15 mm Use a thin object to reach the key e g a 1 5 mm wire 4 Maintenance WARNING Risk of injury caused by components moved automatically The automatic control can start system components and place people in danger e g mo...

Страница 15: ...rtümer vorbehalten The device must regularly be checked for dirt twice a year and cleaned if necessary In case of severe dirt the sensor may not work properly anymore ATTENTION The device can be damaged if water penetrates the housing Do not clean with high pressure cleaners or steam jets ...

Страница 16: ... 36 Rain Switching delay to rain Input WC 7 005 DPT_TimePeri odSec 2 bytes 37 Rain Switching delay to no rain Input WC 7 005 DPT_TimePeri odSec 2 bytes 41 Temperature sensor Malfunction Output R CT 1 1 DPT_Switch 1 bit 42 Temperature sensor External meas urement Input SKÜ 9 1 DPT_Value_Temp 2 bytes 43 Temperature sensor Measurement value Output R CT 9 1 DPT_Value_Temp 2 bytes 44 Temperature sensor...

Страница 17: ...Temp threshold value 3 Switching delay from 0 to 1 Input WC 7 5 DPT_TimePeriod Sec 2 bytes 68 Temp threshold value 3 Switching delay from 1 to 0 Input WC 7 5 DPT_TimePeriod Sec 2 bytes 69 Temp threshold value 3 Switching output Output R CT 1 1 DPT_Switch 1 bit 70 Temp threshold value 3 Switching output block Input WC 1 1 DPT_Switch 1 bit 72 Temp threshold value 4 Absolute value Input Output RWCT 9...

Страница 18: ...tput block Input WC 1 1 DPT_Switch 1 bit 115 Brightness sensor threshold value 3 Absolute value Input Output RWCT 9 4 DPT_Value_Lux 2 bytes 116 Brightness sensor threshold value 3 1 0 Input WC 1 1 DPT_Switch 1 bit 117 Brightness sensor threshold value 3 Delay from 0 to 1 Input WC 7 5 DPT_TimePeriod Sec 2 bytes 118 Brightness sensor threshold value 3 Delay from 1 to 0 Input WC 7 5 DPT_TimePeriod Se...

Страница 19: ...put block Input WC 1 1 DPT_Switch 1 bit 143 Brightness sensor 2 threshold value 3 Absolute value Input Output RWCT 9 4 DPT_Value_Lux 2 bytes 144 Brightness sensor 2 threshold value 3 1 0 Input WC 1 1 DPT_Switch 1 bit 145 Brightness sensor 2 threshold value 3 Delay from 0 to 1 Input WC 7 5 DPT_TimePeriod Sec 2 bytes 146 Brightness sensor 2 threshold value 3 Delay from 1 to 0 Input WC 7 5 DPT_TimePe...

Страница 20: ...utput block Input WC 1 1 DPT_Switch 1 bit 171 Brightness sensor 3 threshold value 3 Absolute value Input Output RWCT 9 4 DPT_Value_Lux 2 bytes 172 Brightness sensor 3 threshold value 3 1 0 Input WC 1 1 DPT_Switch 1 bit 173 Brightness sensor 3 threshold value 3 Delay from 0 to 1 Input WC 7 5 DPT_TimePeriod Sec 2 bytes 174 Brightness sensor 3 threshold value 3 Delay from 1 to 0 Input WC 7 5 DPT_Time...

Страница 21: ...utput block Input WC 1 1 DPT_Switch 1 bit 199 Total brightness threshold value 3 Absolute value Input Output RWCT 9 4 DPT_Value_Lux 2 bytes 200 Total brightness threshold value 3 1 0 Input WC 1 1 DPT_Switch 1 bit 201 Total brightness threshold value 3 Delay from 0 to 1 Input WC 7 5 DPT_TimePeriod Sec 2 bytes 202 Total brightness threshold value 3 Delay from 1 to 0 Input WC 7 5 DPT_TimePeriod Sec 2...

Страница 22: ... 1 1 DPT_Switch 1 bit 227 Twilight brightness threshold value 3 Absolute value Input Output RWCT 9 4 DPT_Value_Lux 2 bytes 228 Twilight brightness threshold value 3 1 0 Input WC 1 1 DPT_Switch 1 bit 229 Twilight brightness threshold 3 delay from 0 to 1 Input WC 7 5 DPT_TimePeriod Sec 2 bytes 230 Twilight brightness threshold 3 delay from 1 to 0 Input WC 7 5 DPT_TimePeriod Sec 2 bytes 231 Twilight ...

Страница 23: ...Delay from 1 to 0 Input WC 7 5 DPT_TimePeriod Sec 2 bytes 285 Wind threshold value 1 Switching out put Output R CT 1 1 DPT_Switch 1 bit 286 Wind threshold value 1 Switching out put block Input WC 1 1 DPT_Switch 1 bit 287 Wind threshold value 2 Absolute value Input Output RWCT 9 5 DPT_Value_Wsp 2 bytes 288 Wind threshold value 2 1 0 Input WC 1 1 DPT_Switch 1 bit 289 Wind threshold value 2 Delay fro...

Страница 24: ...PT_Switch 1 bit 1149 Computer 2 Input I1 Input RWCT 4 bytes 1150 Computer 2 Input I2 Input RWCT 4 bytes 1151 Computer 2 Input I3 Input RWCT 4 bytes 1152 Computer 2 Output O1 Output R CT 4 bytes 1153 Computer 2 Output O2 Output R CT 4 bytes 1154 Computer 2 Condition text Output R CT 16 0 DPT_String_AS CII 14 bytes 1155 Computer 2 Monitoring status Output R CT 1 1 DPT_Switch 1 bit 1156 Computer 2 Bl...

Страница 25: ...lock 1 block Input WC 1 1 DPT_Switch 1 bit 1189 Computer 7 Input I1 Input RWCT 4 bytes 1190 Computer 7 Input I2 Input RWCT 4 bytes 1191 Computer 7 Input I3 Input RWCT 4 bytes 1192 Computer 7 Output O1 Output R CT 4 bytes 1193 Computer 7 Output O2 Output R CT 4 bytes 1194 Computer 7 Condition text Output R CT 16 0 DPT_String_AS CII 14 bytes 1195 Computer 7 Monitoring status Output R CT 1 1 DPT_Swit...

Страница 26: ...PT_TimeOfDay 3 bytes 1229 Weekly timer period 5 Switching out put Output R CT 1 1 DPT_Switch 1 bit 1230 Weekly timer period 5 8 bit output Output R CT 5 10 DPT_Value_1_U count 1 byte 1231 Weekly timer period 6 Switch on time Input RWCT 10 1 DPT_TimeOfDay 3 bytes 1232 Weekly timer period 6 Switch off time Input RWCT 10 1 DPT_TimeOfDay 3 bytes 1233 Weekly timer period 6 Switching out put Output R CT...

Страница 27: ...riod 12 Switch off time Input RWCT 10 1 DPT_TimeOfDay 3 bytes 1257 Weekly timer period 12 Switching out put Output R CT 1 1 DPT_Switch 1 bit 1258 Weekly timer period 12 8 bit output Output R CT 5 10 DPT_Value_1_U count 1 byte 1259 Weekly timer period 13 Switch on time Input RWCT 10 1 DPT_TimeOfDay 3 bytes 1260 Weekly timer period 13 Switch off time Input RWCT 10 1 DPT_TimeOfDay 3 bytes 1261 Weekly...

Страница 28: ...riod 18 Switch off time Input RWCT 10 1 DPT_TimeOfDay 3 bytes 1281 Weekly timer period 18 Switching out put Output R CT 1 1 DPT_Switch 1 bit 1282 Weekly timer period 18 8 bit output Output R CT 5 10 DPT_Value_1_U count 1 byte 1283 Weekly timer period 19 Switch on time Input RWCT 10 1 DPT_TimeOfDay 3 bytes 1284 Weekly timer period 19 Switch off time Input RWCT 10 1 DPT_TimeOfDay 3 bytes 1285 Weekly...

Страница 29: ... CT 1 1 DPT_Switch 1 bit 1306 Weekly timer period 24 8 bit output Output R CT 5 10 DPT_Value_1_U count 1 byte 1331 Calendar timer period 1 Start date Input RWCT 11 1 DPT_Date 3 bytes 1332 Calendar timer period 1 End date Input RWCT 11 1 DPT_Date 3 bytes 1333 Calendar timer period 1 sequence 1 Switch on time Input RWCT 10 1 DPT_TimeOfDay 3 bytes 1334 Calendar timer period 1 sequence 1 Switch off ti...

Страница 30: ...ching output Output R CT 1 1 DPT_Switch 1 bit 1356 Calendar timer period 3 sequence 1 8 bit output Output R CT 5 10 DPT_Value_1_U count 1 byte 1357 Calendar timer period 3 sequence 2 Switch on time Input RWCT 10 1 DPT_TimeOfDay 3 bytes 1358 Calendar timer period 3 sequence 2 Switch off time Input RWCT 10 1 DPT_TimeOfDay 3 bytes 1359 Calendar timer period 3 sequence 2 Switching output Output R CT 1...

Страница 31: ... output B Output R CT 1 byte 1414 AND logic 1 Block Input WC 1 1 DPT_Switch 1 bit 1415 AND logic 2 1 bit switching output Output R CT 1 2 DPT_Bool 1 bit 1416 AND logic 2 8 bit output A Output R CT 1 byte 1417 AND logic 2 8 bit output B Output R CT 1 byte 1418 AND logic 2 Block Input WC 1 1 DPT_Switch 1 bit 1419 AND logic 3 1 bit switching output Output R CT 1 2 DPT_Bool 1 bit 1420 AND logic 3 8 bi...

Страница 32: ... 1 byte 1453 OR logic 3 8 bit output B Output R CT 1 byte 1454 OR logic 3 Block Input WC 1 1 DPT_Switch 1 bit 1455 OR logic 4 1 bit switching output Output R CT 1 2 DPT_Bool 1 bit 1456 OR logic 4 8 bit output A Output R CT 1 byte 1457 OR logic 4 8 bit output B Output R CT 1 byte 1458 OR logic 4 Block Input WC 1 1 DPT_Switch 1 bit 1459 OR logic 5 1 bit switching output Output R CT 1 2 DPT_Bool 1 bi...

Страница 33: ...threshold value once set per parameter or via a communication object is retained until a new threshold value is sent via a communication object The last th reshold value set by communication object is saved in the device so that it is retained during a power outage and is available once again when power is restored 6 0 3 Malfunction objects Malfunction objects are sent after every reset and additi...

Страница 34: ...r rect if necessary the output of the measurement value by specifying an offset e g in order to compensate malfunction sources Then set the mixed value calculation if desired Use rain output with fixed switching delay No Yes Delays can be set via objects in seconds No Yes Delay on rain none 1 s 2 h Delay on no rain after drying of the sensor 5 min 1 h 2 h Switching output sends on change on change...

Страница 35: ...l the first call setting via objects is ignored Select whether the threshold value is to be specified per parameter or via a communi cation object When the threshold value per parameter is specified then the value is set When the threshold value per communication object is specified the starting value object value limit and type of change to the threshold value are then set Send pattern never peri...

Страница 36: ... 0 1 C 0 2 C 0 3 C 0 4 C 0 5 C 1 C 2 C 3 C 4 C 5 C Hysteresis setting in absolute Hysteresis in of the threshold value for setting in 0 50 20 Hysteresis in 0 1 C for absolute setting 0 1100 50 When the following conditions apply the output is LV Threshold value GW above 1 GW Hyst below 0 GW above 0 GW Hyst below 1 GW below 1 GW Hyst above 0 GW below 0 GW Hyst above 1 Delays can be set via objects ...

Страница 37: ...ect s send s Switching output sends on change to 1 do not send message If switching output 1 send 1 Switching output sends on change to 0 do not send message If switching output 0 send 0 Switching output sends on change and periodically Send switching output status Switching output sends on change to 1 and periodically If switching output 1 send 1 Switching output sends on change to 0 and periodic...

Страница 38: ...d at the total threshold value in each case a maximum of four The menus for the further set ting of the threshold values are then displayed Send cycle if sent periodically 5 s 2 h 1 min Object value with frost 0 1 Sensor nomenclature S1 Free text Send pattern never periodically on change on change and periodically at and above change in if sent on change 1 100 20 Send cycle if sent periodically 5 ...

Страница 39: ...ue per communication object is specified the starting value object value limit and type of change to the threshold value are then set With both of the methods for specifying the threshold values the hysteresis is set Threshold value No Yes Threshold value 4 No Yes Maintain the threshold values and delays received via communication objects never after power supply restoration after power supply res...

Страница 40: ...elays can be set via objects in seconds No Yes Delay from 0 to 1 none 1 s 2 h Delay from 1 to 0 none 1 s 2 h Switching output sends on change on change to 1 on change to 0 on change and periodically on change to 1 and periodically on change to 0 and periodically Cycle if sent periodically 5 s 2 h Use switching output block No Yes Analysis of the blocking object At value 1 block At value 0 release ...

Страница 41: ...ct whether the threshold value is to be specified per parameter or via a communi cation object When the threshold value per parameter is specified then the value is set When the threshold value per communication object is specified the starting value object value limit and type of change to the threshold value are then set Switching output sends on change to 1 and periodically If switching output ...

Страница 42: ... of the threshold value for setting in 0 100 50 Hysteresis in Lux for absolute setting 0 1000 5 When the following conditions apply the output is LV Threshold value GW above 1 GW Hyst below 0 GW above 0 GW Hyst below 1 GW below 1 GW Hyst above 0 GW below 0 GW Hyst above 1 Delays can be set via objects in seconds No Yes Delay from 0 to 1 none 1 s 2 h Delay from 1 to 0 none 1 s 2 h Switching output ...

Страница 43: ...to be outputted Set the delay for the switching and in which cases the switch output sends and which value is output at night Switching output sends on change do not send message status object s send s Switching output sends on change to 1 do not send message if switching output 1 send 1 Switching output sends on change to 0 do not send message if switching output 0 send 0 Switching output sends o...

Страница 44: ... on change to night on change to day on change and periodically on change to night and periodically on change to day and periodically Send cycle if sent periodically 5 s 2 h Object value at night 0 1 Use malfunction object No Yes Measured value additionally output in the Beaufort scale No Yes Send pattern never periodically on change on change and periodically on change of if sent on change 2 5 10...

Страница 45: ... are always used until the first call setting via objects is ignored Select whether the threshold value is to be specified per parameter or via a communi cation object When the threshold value per parameter is specified then the value is set When the threshold value per communication object is specified the starting value object value limit and type of change to the threshold value are then set 9 ...

Страница 46: ...ep size upon increase decrease change 0 1 m s 0 2 m s 0 5 m s 1 0 m s 2 0 m s 5 0 m s Hysteresis setting in absolute Hysteresis in relative to threshold value for setting in 0 100 50 Hysteresis in 0 1 m s for absolute setting 0 350 20 When the following conditions apply the output is LV Threshold value GW above 1 GW Hyst below 0 GW above 0 GW Hyst below 1 GW below 1 GW Hyst above 0 GW below 0 GW H...

Страница 47: ... are always used until the first call setting via objects is ignored Action when locking Do not send message send 0 send 1 Action upon release with 2 seconds release delay Dependent on the Switching output sends setting Switching output sends on change do not send message Status object s send s Switching output sends on change to 1 do not send message If switching output 1 send 1 Switching output ...

Страница 48: ...t Calculation Output 1 E1 X Y Output 2 E2 X Y Transformation General Tolerance for comparison in the case of prerequisite E1 E2 0 4 294 967 295 Input type Selection options depending on the func tion 1 bit 1 byte 0 255 1 byte 0 100 1 byte 0 360 2 byte counter without math symbol 2 byte counter with math symbol 2 byte floating point 4 byte counter without math symbol 4 byte counter with math symbol...

Страница 49: ...nput range depending on the type of output Output sends on change on change and after reset on change and periodically when receiving an input object when receiving an input object and periodically Type of change is only sent if on change is selected on each change on change to condition met on change to condition not met Send cycle if sent periodically 5 s 2 h 10 s Text if the condition is met Fr...

Страница 50: ...t a 1 or 0 at the block entry means and what happens in the event of a block Output sends on change on change and after reset on change and periodically when receiving an input object when receiving an input object and periodically on change of only if calculations are transmitted for changes 1 Input range depending on the type of input Send cycle if sent periodically 5 s 2 h 10 s Formula for outp...

Страница 51: ...od 1 24 Set whether the period can be set period object is the output and is sent to the bus or if the period is received externally via the bus period object is the input Period can be set time period object is output Set whether the switching times are set per object and in which cases the switching times received are to be retained Please note that the setting After power restoration and progra...

Страница 52: ... In the calendar timer in the device four periods with two switching sequences can be defined Activate the required periods for the calendar timer The menus for the further setting of the computer are then loaded Switch on time hours 0 23 Switch on time minutes 0 59 Switch off time hours 0 23 Switch off time minutes 0 59 Period switches to Monday Sunday No Yes Switching output sends never on chang...

Страница 53: ... period Sequence 1 2 Define the switching times Use objects for switching times No Yes Maintain the switching data and times received via com munication objects never after power restoration after power restoration and programming From Month January December Day 1 29 1 30 1 31 according to month Up to and including Month January December Day 1 29 1 30 1 31 according to month Switch on time hours 0...

Страница 54: ...etting options are available for AND and OR logic Switching output sends never on change on change to active on change to inactive on change and periodically on change to active and periodically on change to inactive and periodically Send cycle if sent periodically 5 s 2 h 10 s 8 bit output value if Period active 0 255 8 bit output value if Period not active 0 255 Use logic inputs Yes No Object va...

Страница 55: ... and Verknüpfungseingänge der ODER Logik Seite 100 Output type a 1 Bit object two 8 bit objects Output value if logic 1 1 0 Output value if logic 0 1 0 Output value If block is active 1 0 Output value if monitoring period is exceeded 1 0 Object type Value 0 255 Percent 0 100 Angle 0 360 Scene call up 0 127 Output value object A if logic 1 0 255 100 360 127 1 Output value object B if logic 1 0 255 ...

Страница 56: ...o 0 on change of logic and periodically on change of logic to 1 and periodically on change of logic to 0 and periodically on change of logic object receipt on change of logic object receipt and periodically Send cycle if sent periodically 5 s 10 s 2 h Use block No Yes Analysis of the blocking object At value 1 block At value 0 release At value 0 block At value 1 release Blocking object value befor...

Страница 57: ...put 10 inverted Logic input 11 Logic input 11 inverted Logic input 12 Logic input 12 inverted Logic input 13 Logic input 13 inverted Logic input 14 Logic input 14 inverted Logic input 15 Logic input 15 inverted Logic input 16 Logic input 16 inverted Temperature sensor malfunction ON Temperature sensor malfunction OFF Pressure sensor malfunction ON Pressure sensor malfunction OFF GPS malfunction ON...

Страница 58: ...t Switching output 1 Twilight inverted Switching output 2 Twilight Switching output 2 Twilight inverted Switching output 3 Twilight Switching output 3 Twilight inverted Switching output 4 Twilight Switching output 4 Twilight inverted Switching output 1 Pressure Switching output 1 Pressure inverted Switching output 2 Pressure Switching output 2 Pressure inverted Switching output 3 Pressure Switchin...

Страница 59: ...od 15 active Weekly timer period 15 inactive Weekly timer period 16 active Weekly timer period 16 inactive Weekly timer period 17 active Weekly timer period 17 inactive Weekly timer period 18 active Weekly timer period 18 inactive Weekly timer period 19 active Weekly timer period 19 inactive Weekly timer period 20 active Weekly timer period 20 inactive Weekly timer period 21 active Weekly timer pe...

Страница 60: ...nce 2 active Calendar timer period 4 sequence 2 inactive 6 14 3 Connection inputs of the OR logic The OR logic connection inputs correspond to those of the AND logic In addition the following inputs are available for the OR logic AND logic output 1 AND logic output 1 inverted AND logic output 2 AND logic output 2 inverted AND logic output 3 AND logic output 3 inverted AND logic output 4 AND logic ...

Страница 61: ... 60184 white 60185 60189 black WS1 Style PF 60191 60194 white 60196 60199 black WS1000 Style 60201 60204 white 60206 60209 black WS1000 Style PF 60211 60214 white 60216 60219 black Elsner Elektronik GmbH Control and AutomationTechnology Sohlengrund 16 75395 Ostelsheim Phone 49 0 7033 30945 0 info elsner elektronik de Germany Fax 49 0 7033 30945 20 www elsner elektronik de Technical support 49 0 70...

Отзывы: