Parameter setting
Actuator KNX S1R-BA4-UP 24 V
• Version: 27.05.2020 • Technical changes and errors excepted.
step operation the temperature/humidity deviation is checked after a specified period
of time, and may be increased/decreased by one step.
6.2.1.6.Scenes (drives)
A group address for scenes
must be filed in the KNX system to control the scenes.
The input object ‘Channel X: call/save scenes’ of the actuator is linked to this group
address.
A scene is
called
, then the
scene number
is communicated to the actuator. The
movement position saved for this scene number in the actuator is then taken.
If the scene
saving
function is used, then the current movement position is saved for
this scene number in the actuator.
The ‘Scenes’ menu item of the actuator is only shown if ‘Use scenes: yes’ was selected
in the settings for the drive channel. Every drive can
have up to 16 scene save
points
for movement positions.
Activate a scene save point.
Assign a scene number to the scene save point. Use this scene number to call/save the
movement position stored in the actuator. Make sure that every scene number is used
only once per drive channel.
Set the movement position. If it is allowed to save scenes via the bus, this position only
applies after the ETS download until the first manual saving. Afterwards, the new
movement position saved in the actuator is used.
6.2.1.7.Button inputs (drives)
Depending on the model, there are no inputs, two or four inputs.
Window opening
absolute in % • incrementally
Window opening in %
(only if "window opening is absolute in %")
1...100
incrementally by (in %)
(only if "window opening is in increments")
1...100; 25
every (in minutes)
(only if "window opening is in increments")
1...60; 3
Use scene save point X
no •
yes
Scene number
0...127
Shutter position in % or
Blind position in % or
Awning position in % or
Window position in %
0...100; 50
Slat position in %
(only for shutters)
0...100; 70