106
Basic Setting
Control System WS1 Color / WS1000 Color
• Version: 14.12.2016 • Technical changes and errors excepted.
Select the button of the appropriate contact. Confirm your selection with the
OK
but-
ton.
Press the button in the basic settings to assign an installed door contact to a sliding
door. Select the button of the appropriate contact.
Confirm your selection with the
OK
button.
Press the button to set wheather the drive should be displayed in the manuel menue
or not.
Confirm your selection with the
OK
button.
Tips on connecting windows
With windows the supply of fresh air can be very well regulated using the Step window
configuration. In this, the control unit checks the room temperature every 3 minutes. If
the temperature is close to the reference value, the window will be opened or closed
step by step. You can adjust the number of steps in the Automation menu (“Number
of steps” button).
For sliding roofs, during normal operation of ventilators, it is not necessary to use the
full stroke. For that reason you can adjust the size of the opening in the Automatic
menu (“Movement position” button). If the sliding roof should be opened fully, this
can take place manually.
ATTENTION
Material damage due to use of step/sliding roof operation with
inappropriate window motors!
Not all window motors are suitable for step/sliding mode.
•Use this functions only with motors that are qualified for step/sliding
operation by the manufacturer.
6.1.2. Assign external buttons
If external buttons for operating drives and devices on the spot are installed, their set-
tings and assignments can be made here.
Single buttons
(toggle buttons) can be installed and allocated the function
Button
.
Equipment such as heating, cooling, ventilation, lighting and/or gutter heating are
thereby switched on and off alternately.
To be able to control a dimmer, the single button must be allocated the function of the
Button
.
Closed Detector
Manual Menue