The voltage on the B+ stud of the
controller is too far from B+ when the
line contactor is off.
F/F
Factory Override
4/4
Funtion Locked-Battery
Battery voltage is too low or too high to
allow movement.
Check the wiring.
4/4
The battery supply is too low.
The battery must be re-charged.
4/4
The battery supply is too high.
Check that the correct battery and charger
are installed.
6/6
CAN BUS
CANbus messages expected from one
or more modüle are nor being
received, or messages intended to one
or more modüle cannot be transmitted.
Check
for
open-
and
short-circuit
problems with CANbus wiring; ensure that
the CANbus is wired correctly pin-to-pin;
ensure that the machine chassis is not
erroneusly shorted to the motor wiring.
This procedure should perform with the
firm.
4/1
Bad Internal Temperature Sensor
The heatsink temperature is out of
range.
The power controller may have to be
replaced.
4/2
Bad Internal 5V
The internal 5V slave supply is out of
range.
The controller may have to be replaced.
4/2
Bad Internal slave
The internal slave is nor operating
correctly.
The controller may have to be replaced.
4/3
Bad Internal 12V
The internal 12V supply is out of range.
The controller may have to be replaced.
9/9
Some Big Bad Problem!