The scheme beside shows briefly, how the dataline 

wiring of several controllers via the 'network/line' 

interface is made. At each controller, the shield has 

to be connected to the nearest ground terminal 

(PE). Also the ground connector of the controller 

(term.1) and terminal #24 must be connected to 

the nearest ground terminal.

This will assure good interference suppression, 

even for long datalines between the controllers.

The MSR 

eco

 can be used as a Central Unit for 

up to 64 Cold Storage Controllers of the series 

EVP and TKP. These can be connected via a 

separate network interface. 

Shielding must be connected to the nearest ground 

terminal. Also the ground connector of the controller 

(term.1) and terminal #24 must be connected to 

the nearest ground terminal.  

Each  connected  controller  gets  an  individual 

address, which must be set at the controller and 

on the Address Page (A) under 

A00...A63

Thus, data can be centralized and forwarded for 

optimization of the control functions.

On  the  ‚Address  Page‘,  the  controller  ‚type‘ 

must be selected via ‚

d01

‘ for each address, as 

well  as  the  influence  on  the  suction  pressure 

shifting of the MSR 

eco

 via ‚

d02

 and 

d03

‘ for 

each address.

Connection of Cold Storage Controllers as Slaves

 Wiring of data lines (Network Line)

 Networking of controllers via 

E-LINK

The  MSR 

eco

  can  be  networked  together  with 

other ELREHA control devices via an RS-485-2-

wire databus, which enables up to 78 controllers 

to communicate. For communication, the 

E-LINK

 

transmission protocol is used. 

Each  controller  in  a  network  has  its  individual 

address ('

P90

', Mode Page). 

!! Never use address 64 !!

The data transmission rate is factory set to "96" 

(9600 Baud) and

 can also be set manually ("

P89

", 

Mode Page). 

If the MSR 

eco

 is not connected to a network, these 

parameters are of no importance. 

 

Remote control at Frontend Systems

The MSR 

eco

 controller can be operated remotely 

via  interface  when  it  is  connected  to  Frontend 

Systems such as an SMZ. 

In this case, the Frontend System shows the display 

contents and the keys of the frontend work as if 

they where the keys of the MSR 

eco

 .

Configuration / Service via PC

The controller can be linked to a PC via its RS-485 

interface. By using the PC-software „Coolvision-

MES“, parameters can be changed, they can be 

saved to the hard disk (download) and can be sent 

to the controllers (upload). 

To do this, the PC must be equipped with an RS-

485 interface (internal card or a converter of the 

SSC-series).

Note

Protective Earth

Earth

Note

Protective Earth

Earth

RS-485 (network line) 

up to any 64 modules

relay 

K1

N

1

2

3

L

4

5

6

7

24

21

20

23

22

25 26

RS

485

NDO

DO

RS

485

NDO

DO

RS

485

NDO

DO

relay 

K1

N

1

2

3

L

4

5

6

7

24

21

20

23

22

25 26

RS

485

NDO

DO

RS

485

NDO

DO

RS

485

NDO

DO

MSR 

eco

 3140

MSR 

eco

 3140

RS-485 (Slave-Module) 

up to 64 Cold Storage 

Controllers

relay 

K1

N

1

2

3

L

4

5

6

7

24

21

20

23

22

25 26

RS

485

NDO

DO

RS

485

NDO

DO

RS

485

NDO

DO

N

1

2

3

L

4

5

24

21

20

23

22

RS

485

NDO

DO

25 26

6

N

1

2

3

L

4

5

24

21

20

23

22

RS

485

NDO

DO

25 26

6

MSR 

eco

 3140

EVP 3167/3168

EVP 3167/3168

Содержание MSR eco 3140

Страница 1: ...n the Actual Values Page at L98 and L99 Programming The MSR eco parameters are simple to access view and change During normal operation or if no key is pressed for at least 3 minutes the MSR eco will...

Страница 2: ...current typ 1mA 4 20 mA max shunt resistance 500 ohms Display Parameter Ranges see parameter pages Data Interfaces 3x RS 485 Data Storage unlimited Real Time Clock automatic summer winter switch 10 d...

Страница 3: ...pecific sensor So1 40 25 C customer specific sensor So2 50 50 C The type of sensor can be set by h20 Assignment Page Pressure Transmitter Pressure Transmitters with 4 20mA output can be used They must...

Страница 4: ...SP 0 8 stages L43 X 3 2 1 Number of running stages of motor 3 SP 0 8 stages L44 X 3 2 1 Number of running stages of motor 4 SP 0 8 stages L45 X 3 2 1 Number of running stages of motor 5 SP 0 8 stages...

Страница 5: ...nimal superheat 0 0 25 0 K 0 0 K 0 0 K 0 0 K 0 0 K 0 0 K switched off P15 oem 3 2 Compound lock delay minimal superheat 5 900 sec 5 sec 5 sec 5 sec 5 sec P20 oem 3 2 Sending date and time to connected...

Страница 6: ...0 sec 1 sec 1 sec 1 sec 1 sec r29 oem 3 2 VBR Forerun Backrun Range Time max 1 900 sec 20 sec 20 sec 20 sec 20 sec r41 3 2 1 Forerun Delay Time stage 1 the first turn on stage 0 900 sec 10 sec 10 sec...

Страница 7: ...sec 0 sec 0 sec 0 sec d51 tec 3 2 Backrun Delay Time Stage 1 the last off stage 0 900 sec 10 sec 0 sec 0 sec 0 sec d52 tec 3 2 Backrun Delay Time Stage 2 0 900 sec 10 sec 0 sec 0 sec 0 sec d53 tec 3...

Страница 8: ...tages SP motor 3 0 8 0 1 1 1 h54 tec 3 2 Number of stages SP motor 4 0 8 0 0 0 0 h55 tec 3 2 Number of stages SP motor 5 0 8 0 0 0 0 h56 tec 3 2 Number of stages SP motor 6 0 8 0 0 0 0 h57 tec 3 2 Num...

Страница 9: ...ng S2 Relais K2 1 2 4 3 5 Relais K1 Digital eingang DI 1 6 10 7 9 8 Relais K3 Relais K4 Digital eingang DI 2 20 23 24 21 22 19 16 17 18 DO NDO GND Netz werk 13 14 relay K1 N 1 2 3 L 4 5 6 7 8 9 1 24 2...

Страница 10: ...cted to the device Wire should be 0 5mm at a minimum Mounting the device in close proximity to power relays is NOT recommended Strong electro magnetic interference may cause the device to malfunction...

Страница 11: ...trol method can be activated by the pa rameter h49 With this method only one of the compressors can be controlled Characteristicforthiscompressortypeisthefactthat the first stage generates no refriger...

Страница 12: ...ctivated if the suction pressure goes beyond the hysteresis range Above and below the hysteresis range are definable areas VBR Forerun Range r41 respective VBR Backrun Range r42 If the suction pressur...

Страница 13: ...01 h09 Any of these relays can also be switched on manually The relay output is switched OFF on The relay output is switched ON manually permanent alA Warning Alarm SuA Warning Suction Overheat L1 The...

Страница 14: ...bus which enables up to 78 controllers to communicate For communication the E LINK transmission protocol is used Each controller in a network has its individual address P90 Mode Page Never use address...

Страница 15: ...valve 1 3 St 4 CRII valve 1 2 St 3 Motor 1 CR St 1 CRII valve 1 1 St 2 1 0 1 1 1 4 0 0 0 1 Conv Compressor 20 2x1 stages Alarm Motor 1 Stage1 Motor 2 Stage 2 0 0 0 0 0 1 1 0 0 0 21 3x1 stages Alarm M...

Страница 16: ...11 2016 A1 2017 EN 61010 1 2010 EN 61326 1 2013 CE marking of year 2018 This statement is made for the manufacturer importer by ELREHA Elektronische Regelungen GmbH Werner Roemer Technical Director D...

Отзывы: