background image

Technical Manual Stage Controller MSR 

eco

 3140

Page  11

 Functional Description

Input Signals of the Controller

The  input  signals  come  from  a  2-wire  pressure 

transmitter with a 4-20 mA signal or one of the four 

(4) temperature probes. The source can be selected 

at 

h21

...

h26

 (Assignment page). 

If  a  pressure  transmitter  is  selected,  additionally 

a  refrigerant  must  be  defined  (at 

h99

),  which  is 

necessary to calculate a temperature in °C. 

Calibration of Transmitter, Display Correction

For each transmitter input must be defined, which 

pressure  corresponds  to  the  delivered  4-20  mA 

signals. 
 

4-20mA Input

  For this inputs, the matching pressure limits can  

  be set by 

h93

h94

 (pressure transmitter input 1)  

  and 

h95

h96

 (pressure transmitter input 2).

Probe-/Transmitter Failures

If a probe or transmitter failure is identified, all stages 

will switch ON with the selected delay. 

After the alarm delay 

r08

, the alarm relay (

ALA

switches off if it is defined and available. 

Control of Compressors (Load)

The MSR 

eco

 is able to control up to 8 (with extension 

module BMR 3002) single or multi-stage loads with 

up to four stages. 

The  kind  and  number  of  stages  of  the  selected 

loads must be defined with the parameters 

h51

 up 

to 

h58

.  

Example:

Standard Stage Controller

Applications include:

-  Standard compressors

-  Compressors with 

  CRII Control Stages / Power Control

-  Condensation High Pressure Control

Standard Compressors (SP)

The control setpoint is preset by 

r01

 (day) or 

r02

 

(night). With 

r03

 a maximum value for this setpoint 

can be determined. The range of the hysteresis can 

be set using parameter 

r04

, while 

r05

 determines 

the position above the set point, (above, below, or 

balanced). 
Forerun (Stages ON)

If  the  actual  value  exceeds  the  switching  point, 

then the forerun delay starts (

r41

...

r48

, individual 

for each stage). After this timer is run down, a stage 

will be switched ON and the individual delay time 

starts again. 
Neutral Zone

If the actual value  is located within the hysteresis 

range 

r04/r05

, no stage will be activated or 

de-activated.
Backrun (Stages will switch OFF) 

If  the  actual  value  falls  below  the  tripping  point, 

the  backrun  delay  (

r51

...

r58

,  individual  for  each 

stage) will be started. After this timer is run down, 

one stage will switch OFF and the individual delay 

time starts again.

 L21

 shows the current state of the 

 controller.

Limits

If the actual measured value falls to a critical 

level, the controller will react in two ways:

If the actual value falls below the Early Warning 

Alarm setpoint, parameter ‚

r07

‘, then at least 50% 

of the motors will switch off, once the set time of 

parameter ‚

r08

‘ is reached.   

If the actual value falls below parameter ‚

r06

‘, 

then a forced Backrun will also be initiated, 

shutting down all motors.

Compressor

 

Programming    Relay selection

 

  

 

 

 

  free at

 

h51  h52  h53  h54   

h01 ... h05

4x single mach. 

1  1  1  1 

 

2x dual stage 

2  2  0  0 

1x 3-stage 

3  0  0  0 

1x 3-stage and 
1x single mach. 

3  1  0  0 

Base Load Change / Switching Frequency Opt.

If a plant is laid out correctly, then not all fans and 

compressors should run continuously.  When 

using normal stage controllers, some motors bear 

a heavy load while other hardly any load at all.  To 

prevent this, the „Base Load Change“ function can 

be utilized. (This function is also known as Stage 

Sequencing).
The „

r22

“ parameter monitors the relative run 

times of the motors and will establish a consistent 

balance of approximately the same runtime for 

each motor.  Different application scenarios can be 

selected.  If a multistage unit is being used, only 

the runtime of the leading stage, (=motor on) will 

be calculated.  

The control system records and stores the runtime 

and downtime of each motor to determine which 

motor can be switched on or off. 
During „Backrun“ operation, the motor with the 

longest run time will be switched off first.  For the 

„Forerun“ operation, the option exists to select the 

motor based on (

a

) shortest runtime, or (

b

) longest 

downtime.
If the pressure ratio in the plant does not change 

over a long period of time, no 'Forerun/Backrun' is 

active and a sequencing is impossible. The 'Delay 

Time (

r20

) starts a short backrun after the set time 

to enable a new motor selection.

It is also possible to select an optimization function, 

(

c

), for the switching frequency.  If the optimization 

function is activated, during backrun, the controller 

switches off an additional stage on a compressor 

before a motor is switched off. 

Thus, a more uniform utilization can be 

achieved without any particular motor car-

rying an unnecessary higher load.

With 

r21

  an  Operational-Feedback  Time  can  be 

set,  which  determines  when  a  feedback  signal 

must be recognized. 

Minimum Idle Time

If a motor is switched off, it can be restarted after a 

Minimum Idle Time (

r71

...

r78

).

Control of Compressors with

CRII-System Power Control

This control method can be activated by the pa-

rameter "

h49

". With this method, only one of the 

compressors can be controlled. 

Characteristic for this compressor type is the fact that 

the first stage generates no refrigeration capacity. 

The control of the refrigeration capacity is achieved 

by a fast on/off switching of the power stages.

Control

The control of the CRII-Valves is always inverted, 

that means if voltage appears at the corresponding 

output, the respective power stage is deactivated. 

The switching behaviour must be set separately 

for  each  power  stage  (inverted  for  CRII-power 

stages, 

h61

...

h68

).

While a standstill, the CRII-Valves of the motor will 

be de-energized. With the start of the motor the 

switching outputs of the power stages will be 

utlized at the same time.

If the motor runs without power stages, an 

adjustable „switch-off“ countdown  "

r24

" will be 

initiated.  Once the set amount of time is depleted, 

the motor will be switched off.

The controller performs regular sequence 

exchanges to ensure the CRII Valves switch an 

equal number of times.

The forerun/backrun behaviour is the same as at 

the standard application.

Toggling of Power Stages

If the power requirement develops in the way that 

a  power  stage  switches  repeatedly,  the  forerun/

backrun delay times are not used, but the 

respective stage can be switched on/off 

immediately after "

r23

“ (

Idle Time of the stage with 

0% load

). 

Base Load Change with Switching Frequency 

Optimization at Backrun

Due to the special requirements of the control de-

pending on the basic stage, the Switching 

Frequency Optimization does not work and must 

be de-activated. So only the values "000, rr0, hr0“ 

are allowed for the parameter "

r22

“. 

"rr1" and "hr1" are treated as "rr0" and "hr0" 

respectively.

Condensation High Pressure Control (HP)

The  Condensation  High  Pressure  Control  can 

be used with the analogue output as P-controller 

and/or with up to 8 relay stages. The relay stages 

can be assigned to up to 8 machines. For each 

stage a forerun delay time (

d41

...

d48

), a backrun 

delay time (

d51

...

d58

) and a setpoint (

d01

...

d08

is available. Each motor can be set to manually/off/

automatic (

d61

...

d68

) as well as a minimum idle  

time (

d71

...

d78

). 

The HP function has the same base-load change 

function and switching optimization as the SP

function. HP  operates  with  an  unified  control  

hysteresis (

d12

) and  hysteresis  position (

d13

), 

relative to the active setpoint.

Depending in the number of stages that are on, the 

On/Off Switch position will be depended on the 

respective  setpoint  -  hysteresis  respectively  the 

next se hysteresis. With it, the position of 

the hysteresis is taken into account. When using 

the analogue output P Controller, the proportional 

range is determined by the switch-on/off positions 

of the respective stage, depending on the number 

of running stages. If the configuration has only one 

or zero stages, the switch-on/off positions are 

represented by the first setpoint and the hysteresis 

of the stage controller only.
Two  (2)  limit  values  'High  pressure  alarm  limit' 

(

d17

) and 'High pressure pre alarm limit' (

d18

generate error messages when exceeded. 

If 

d18

 is exceeded, a load limitation of the SP 

machines  will  be  activated  to  max  75%  of  the 

selected machines. If 

d17

 is exceeded, all SP 

motors will be switched off by fast backrun.

Minimum Overheat Monitoring (SP)

In order to avoid insufficient overheat, and the po-

tential for liquid refrigerant to flow into the suction 

tube, in systems where there may not be enough 

compressor power to create sufficient overheat, 

the „Minimum Superheat Threshold“, parameter 

P10

‘ should be used. When the established mini-

mum limit is not reached, an alarm will be triggered 

and the expansion valves of the cooling positions 

will be locked with special settings.
An additional temperature probe (Sut) would need 

to be installed at the suction tube. The suction gas 

overheat will be calculated using the measured 

temperature value at the suction tube and the 

suction pressure transmitter.
If ‚

P10

‘ is not reached, and ‚

P12

‘, („Superheat 

Warning Delay Timer“) times out, then an „SSG 

Warning“ alarm will be activated, and if needed, 

the cooling positions will be locked.
The backrun of the last running compressor stages 

will not be generated at the standard switch point, 

but the compound sucks up to the defined suction 

pressure pre-warning setpoint, and switches off 

without delay.

If the overheat has reached the defined limit value 

+ hysteresis, the warnings and cooling position 

locks will be canceled.
If  the  overheat  falls  below  a  second  limit  value 

(Compound  lock  threshold  minimal  superheat, 

P14

), which is smaller than the first limit value, 

after the settable delay time (

P15

) a fast backrun 

of the compound will be started and an alarm 'SSG 

fault' appears. 
The  delay  for  the  switch-off  starts  earliest,  after 

the alarm delay (

P12

, warn delay superheat) has 

been run down. The compound will be released if 

the second limit value has been reached again or 

exceeded.

Содержание MSR eco 3140

Страница 1: ...n the Actual Values Page at L98 and L99 Programming The MSR eco parameters are simple to access view and change During normal operation or if no key is pressed for at least 3 minutes the MSR eco will...

Страница 2: ...current typ 1mA 4 20 mA max shunt resistance 500 ohms Display Parameter Ranges see parameter pages Data Interfaces 3x RS 485 Data Storage unlimited Real Time Clock automatic summer winter switch 10 d...

Страница 3: ...pecific sensor So1 40 25 C customer specific sensor So2 50 50 C The type of sensor can be set by h20 Assignment Page Pressure Transmitter Pressure Transmitters with 4 20mA output can be used They must...

Страница 4: ...SP 0 8 stages L43 X 3 2 1 Number of running stages of motor 3 SP 0 8 stages L44 X 3 2 1 Number of running stages of motor 4 SP 0 8 stages L45 X 3 2 1 Number of running stages of motor 5 SP 0 8 stages...

Страница 5: ...nimal superheat 0 0 25 0 K 0 0 K 0 0 K 0 0 K 0 0 K 0 0 K switched off P15 oem 3 2 Compound lock delay minimal superheat 5 900 sec 5 sec 5 sec 5 sec 5 sec P20 oem 3 2 Sending date and time to connected...

Страница 6: ...0 sec 1 sec 1 sec 1 sec 1 sec r29 oem 3 2 VBR Forerun Backrun Range Time max 1 900 sec 20 sec 20 sec 20 sec 20 sec r41 3 2 1 Forerun Delay Time stage 1 the first turn on stage 0 900 sec 10 sec 10 sec...

Страница 7: ...sec 0 sec 0 sec 0 sec d51 tec 3 2 Backrun Delay Time Stage 1 the last off stage 0 900 sec 10 sec 0 sec 0 sec 0 sec d52 tec 3 2 Backrun Delay Time Stage 2 0 900 sec 10 sec 0 sec 0 sec 0 sec d53 tec 3...

Страница 8: ...tages SP motor 3 0 8 0 1 1 1 h54 tec 3 2 Number of stages SP motor 4 0 8 0 0 0 0 h55 tec 3 2 Number of stages SP motor 5 0 8 0 0 0 0 h56 tec 3 2 Number of stages SP motor 6 0 8 0 0 0 0 h57 tec 3 2 Num...

Страница 9: ...ng S2 Relais K2 1 2 4 3 5 Relais K1 Digital eingang DI 1 6 10 7 9 8 Relais K3 Relais K4 Digital eingang DI 2 20 23 24 21 22 19 16 17 18 DO NDO GND Netz werk 13 14 relay K1 N 1 2 3 L 4 5 6 7 8 9 1 24 2...

Страница 10: ...cted to the device Wire should be 0 5mm at a minimum Mounting the device in close proximity to power relays is NOT recommended Strong electro magnetic interference may cause the device to malfunction...

Страница 11: ...trol method can be activated by the pa rameter h49 With this method only one of the compressors can be controlled Characteristicforthiscompressortypeisthefactthat the first stage generates no refriger...

Страница 12: ...ctivated if the suction pressure goes beyond the hysteresis range Above and below the hysteresis range are definable areas VBR Forerun Range r41 respective VBR Backrun Range r42 If the suction pressur...

Страница 13: ...01 h09 Any of these relays can also be switched on manually The relay output is switched OFF on The relay output is switched ON manually permanent alA Warning Alarm SuA Warning Suction Overheat L1 The...

Страница 14: ...bus which enables up to 78 controllers to communicate For communication the E LINK transmission protocol is used Each controller in a network has its individual address P90 Mode Page Never use address...

Страница 15: ...valve 1 3 St 4 CRII valve 1 2 St 3 Motor 1 CR St 1 CRII valve 1 1 St 2 1 0 1 1 1 4 0 0 0 1 Conv Compressor 20 2x1 stages Alarm Motor 1 Stage1 Motor 2 Stage 2 0 0 0 0 0 1 1 0 0 0 21 3x1 stages Alarm M...

Страница 16: ...11 2016 A1 2017 EN 61010 1 2010 EN 61326 1 2013 CE marking of year 2018 This statement is made for the manufacturer importer by ELREHA Elektronische Regelungen GmbH Werner Roemer Technical Director D...

Отзывы: