 4 -  ET8/480, ET8/480S and ET8/480PT - TECHNICAL MANUAL

3. GENERAL FEATURES

For an accurate appraisal, the features of the ET8/480, ET8/480S and ET8/480PT models of control units are as follows:

- Control unit managed by microprocessor for high risk applica-
tions used in residential housing, banks, post offices and busi-
nesses;
 - 

Multi-system functions covering up to four separate

zones with four part-set sections for each zone for total 16
part-set

;

 - 32 user codes and separate installation and programming
code;
 - Built-in control keyboard with integrated proximity key scanner
(only in ET8/480 and ET8/480PT models);
 - Connector for the connection of remote scanner (models I6
and I7) for proximity key;
 - 

16 inputs which can be connected directly to the master

board, expandable up to 80 inputs on serial bus;

 - Inputs can be configured as double balanced or normally
closed;
 - Fully compatible with CP8 series of transponder for serial
expansions;
 - Balanced input for TAMPER protection of system, protection
against opening and removal (against tamper only on ET8/
480PT to protect double door housing with window);
 - 

Self-recognition function of the connected periphericals

,

keyboards and transponders after a total reset;
 - RS485 serial port with terminal board connection to connect
the following type of control devices:
  

AURORA

 = Control and programming keyboard equipped with

back-lit rubber keys, four keys for part setting, a scanner for
electronic proximity keys and a connector for the connection of
other remote readers.
 

 NADIR

 = Control and programming keyboard equipped with a

back-lit display for display purposes, four keys for part setting,
back-lit rubber keys, a scanner for electronic proximity keys and
a connector for the connection of other remote    readers.
 

ZENITH

 = Remote control point, Key point, flush-mounting for

503-type frames equipped with four keys for part setting, a scan-
ner for electronic proximity keys and a connector for the connec-
tion of other remote readers.
 - Accessories to connect to control devices:
 

I6 or I7

 = Scanner point for M4 proximity key connected to key-

board, Key point or directly to the control unit terminal board.
The I6 version is suitable for installation on the MAGIC TICINO
frame; the I7 version on the LIVING TICINO frame.
 - Built-in time programmer for the automatic management of the
system or a portion of it, equipped with 24 programmes with
weekly/annual pattern and management of weekday holidays,
fixed or variable, management of overtime and automatic
changeover between GMT/BST and vice versa;
 - Lithium back-up battery for internal clock;
 - 300 events non-volatile log with FIFO management;
 - Definition of events to be sent to printer and to be recorded in
the log;

-

 Programmability of communications parameters

according to CEI 79-5 and CEI 79-6 protocols;

 - Exit timing programmable in blocks of 1 second for
each individual zone;
 - General alarm timing programmable from 10 seconds
to 600 seconds in blocks of 10 seconds;
 - Delay timing on entry, Pre-alarm, programmable for
each input from 0 to 65535 seconds in blocks of 1 se-
conds;
 - Tamper alarm timing, TAMPER, programmable from 10
seconds to 600 seconds in blocks of 10 seconds;
 - Delay timing for indication mains supply failure pro-
grammable in minutes from 0 to 60;
 - Control unit operating and programming parameters of
the  recorded in NVRAM memory;
 - 

16 programmable electronic MFT outputs

 divided

between two connectors SIGNAL 1 and SIGNAL 2, up to
80 on serial bus;
 - Connector-type output for MP64/DRPT model driver
board for ET848/SIN mimic panel;
 - 

CENTRONICS parallel port

 for printer with connector-

type output;
 - FX/232 optional connector for board with 

2

 

RS232

serial ports

, for connection with centralisations;

 - 

RS232 serial port

 with MINIDIN connector for direct

programming by PC using WINASSIST programme or
dedicated browser with CP8/SER2 cable;
 - 

Up-date of control unit release via PC with DOWN-

LOAD programme and CP8/SER2 cable

;

 - 

RS485 serial port

 with terminal board for serial bus

connection for transponders models CP8/TR8B, CP8/TR,
etc.
 - 

RS485 serial port

 with terminal board for network con-

nection of EL.MO. control units and alarm centralizations.
 - 

C-NA-NC contacts outputs terminal of ALARM and

TAMPER relays;

 - Separate terminals for self-powered sirens control and
for the relative internal battery recharging;
 - Built-in telephone dialler to calls up to 12 telephone
users equipped with telephone line sectioning relay and
connection terminal board; 
 - FAST FORMAT DTMF, SLOW FORMAT EL.Mo PC
AND ADEMCO ID-CONTACT communication protocols;
 - Connector for SK/SINT voice synthesis board connec-
tion for the transmission of two voice messages;
 - Modem section for remote service using WINASSIST;

 - 

New generation 2.5A high efficiency switching power

supply unit, for the mains supply of the system and the
recharging of the buffer battery.

Содержание ET8/480

Страница 1: ...Microprocessor based control units modd ET8 480 ET8 480S and ET8 480PT postal version TECHNICAL MANUAL...

Страница 2: ...mely low percentage of the components used is subjected to faults just as any other electronic or meccanic product As this item is meant to protect both property and people we invite the user to propo...

Страница 3: ...c casing of modern design equipped with a back lit display for the display of operating and programming messages four keys for part setting back lit rubber keys a scan ner for electronic proximity key...

Страница 4: ...the system or a portion of it equipped with 24 programmes with weekly annual pattern and management of weekday holidays fixed or variable management of overtime and automatic changeover between GMT BS...

Страница 5: ...nd by mode CP8 TR8B eight input type transponders 50 mA in stand by mode without outputs connected CP8 TR8 eight input type transponders 50 mA in stand by mode without outputs connected CP8 TR30 conce...

Страница 6: ...st be wall mounted in a suitable position to permit the access of wires for electricity mains supply and telephone line the system alarms wiring the eventual connection of a printer and lastly subsequ...

Страница 7: ...use the upper and the bottom holes you shall use tube box connections with HB or higher flammability rating 5 Connect the transformer s entry terminals to the powered off mains cable inserted in the...

Страница 8: ...8 ET8 480 ET8 480S and ET8 480PT TECHNICAL MANUAL 6 PREARRANGEMENTS View of internal positionings ET8 480 and ET8 480S models View of internal positionings in ET8 480PT model...

Страница 9: ...ecting see fuses table F4 T 5A fuse protecting see fuses table K Connector for the connection of the SK SINT voice synthesis card L Connection terminal board of telephone dialler section with earth te...

Страница 10: ...ample to drive optical acoustic warning devices or inputs for radio links etc ALARM RELAY C NC NA Output terminals of the general alarm relay corresponding to contacts free from potential Contact capa...

Страница 11: ...MANUAL 11 8 ELECTRICAL CONNECTIONS 8 1 Connection of double balanced inputs Main diagram for double balanced connection 8 2 Connection of control unit TAMPER input Main diagram for single balanced con...

Страница 12: ...2nd to 1st 8 4 Connections for control inputs Diagrams for the specific connection of an input for control of the control unit or part of it Note The external source enabling command must be given as...

Страница 13: ...ET8 480S and ET8 480PT TECHNICAL MANUAL 13 8 5 Connection of the transponder Main diagram for transponder connection NOTE The use of CP8 TRS mod transponders is not certificated by IMQ SISTEMI DI SIC...

Страница 14: ...14 ET8 480 ET8 480S and ET8 480PT TECHNICAL MANUAL Diagram of addresses programming for the CP8 TR transponders...

Страница 15: ...ET8 480 ET8 480S and ET8 480PT TECHNICAL MANUAL 15 Diagram of addresses programming for the CP8 TR8 AND CP8 TR8B transponders...

Страница 16: ...ET8 480 ET8 480S and ET8 480PT TECHNICAL MANUAL Connection of transponders mod TR9000 TR9000S and DF9000 NOTE The use of TR9000 and TR9000S transponders is not certificated by IMQ SISTEMI DI SICUREZZ...

Страница 17: ...ET8 480 ET8 480S and ET8 480PT TECHNICAL MANUAL 17 Diagram of TR9000 TR9000S transponders and DF9000 sensor s addresses programming...

Страница 18: ...programmable with MFT functions the first sixteen are located on the master board of the control unit the rest can be used by means of connection to the transponders installed in serial line The MFT t...

Страница 19: ...ET8 480 ET8 480S and ET8 480PT TECHNICAL MANUAL 19 8 8 Connection of a printer 8 9 Connection of a repeater for mimic...

Страница 20: ...m divided up into four zones with the keyboard of the ET8 480 control unit used as supervi sion Note From the connection of a second keyboard up to the wiring of the maximum number of control points i...

Страница 21: ...ET8 480 ET8 480S and ET8 480PT TECHNICAL MANUAL 21 Connection of a NADIR keyboard Connection of AURORA keyboard...

Страница 22: ...ET8 480 ET8 480S and ET8 480PT TECHNICAL MANUAL Connection of a ZENITH Key point Connection of the reader to the keyboard of the ET8 480 control unit Connection of the 2000 model I6 or I7 type reader...

Страница 23: ...s thereby also permitting Remote Service Assistance sessions with the installing company albeit with different ti mings The most interesting aspect is represented by the possibility of installing an o...

Страница 24: ...24 ET8 480 ET8 480S and ET8 480PT TECHNICAL MANUAL Telephone connection example NOTE PTN filter is no certificated from IMQ SISTEMI DI SICUREZZA Example of direct programming from PC...

Страница 25: ...ont keyboard of ET8 480 model control unit View of the keyboard built into the front of the ET8 48 keyboard The ET8 48S only has remote keyboards and the ET8 480PT control unit is equipped with NADIR...

Страница 26: ...26 ET8 480 ET8 480S and ET8 480PT TECHNICAL MANUAL View of the AURORA control keyboard View of ZENITH Key point...

Страница 27: ...keys and after which the following wor ding will appear on the display By pressing the key the various user codes will be visible in programmation and maintenance fase by pressing no codes visualizati...

Страница 28: ...USER NUMBER is the two digit from 01 to 32 identification number of the user in access to command keyboard the user number must be followed by a 6 digit personal code wich allow the full recognition...

Страница 29: ...OG IN MINOR MAINTENANCE LOG IN MUM Access for giving the control unit general or zone based enabling or disabling commands Access for giving the control unit general or zone based enabling or disablin...

Страница 30: ...the changes or by using the key in order to confirm the modifications an acoustic signal will indicate the modification implemented The menu items identified by the lettering MUM are also accessible...

Страница 31: ...numeric nature range 0 65535 Mode D Used for inputting telephone numbers and code number Mode F Mode used for the self learning of the PIT proximity keys to be associated with the various users one ke...

Страница 32: ...0PT TECHNICAL MANUAL Mode H Used for modifying the messages Mode I Used for changing the hexadecimal codes Mode J Used for changing the date displayed and the time of the internal clock and for scroll...

Страница 33: ...ION and 3 for INPUTS DISABLING In this display stage the Firmware version loaded in the internal memory of the control unit is also indicated 14 ACCESS CODE 14 1 Programming code 14 2 User codes User...

Страница 34: ...follow the indications below A Avail of either a portable lap top or a fixed PC in case the operation were taking place in a laboratory B Find the file with BIN extension containing the controlunit s...

Страница 35: ...icon for file loading The following window will be displayed In case it were not visualized use key many times to enter the directory indicated by C Programs ELMO ET480v1L in case of WABL0032 CD prog...

Страница 36: ...fore there is no need to replace the EPROM Upgrade needed before using the file with control units featured by a previous firmware version The browser will give instrunction s to the technician if upg...

Страница 37: ...Open the folder containing the previous version configuration and select it Press open and save with a new name in the version 2 x folder The program will convert the file to a format compatible with...

Страница 38: ...orders consult the user manual NOTE When control unit is supplied for the first time gives enabling system status Keyboards interested to the program ming automaticaly go out from TIMEOUT operative st...

Страница 39: ...PT TECHNICAL MANUAL 39 16 4 Enabling through electronic key 16 5 Enabling in MAXIMUN SECURITY mode 16 6 Disabling the system in MAXIMUN SECURITY mode via keyboard User non authorized to MAXIMUN SECURI...

Страница 40: ...40 ET8 480 ET8 480S and ET8 480PT TECHNICAL MANUAL 17 PROGRAMMING TABLES 17 1 Programming entry COMMAND MODE...

Страница 41: ...ET8 480 ET8 480S and ET8 480PT TECHNICAL MANUAL 41 17 2 ACTIONS menu...

Страница 42: ...42 ET8 480 ET8 480S and ET8 480PT TECHNICAL MANUAL 17 3 SETUP menu...

Страница 43: ...ET8 480 ET8 480S and ET8 480PT TECHNICAL MANUAL 43...

Страница 44: ...44 ET8 480 ET8 480S and ET8 480PT TECHNICAL MANUAL...

Страница 45: ...ET8 480 ET8 480S and ET8 480PT TECHNICAL MANUAL 45...

Страница 46: ...46 ET8 480 ET8 480S and ET8 480PT TECHNICAL MANUAL...

Страница 47: ...ET8 480 ET8 480S and ET8 480PT TECHNICAL MANUAL 47...

Страница 48: ...48 ET8 480 ET8 480S and ET8 480PT TECHNICAL MANUAL...

Страница 49: ...ET8 480 ET8 480S and ET8 480PT TECHNICAL MANUAL 49...

Страница 50: ...50 ET8 480 ET8 480S and ET8 480PT TECHNICAL MANUAL...

Страница 51: ...ol panel s log key flashing in the keyboards indi cate 1 or more inputs disabled Refer to the complete programming manual included in the attached CD for programming details The CD also contains WABL0...

Страница 52: ...technical service point in order to avoid incorrect visualizations and functioning 19 WARNINGS FOR ELIMINATION The control unit s elimination must apply to the municipal provisions in force and shoul...

Страница 53: ...ET8 480 ET8 480S and ET8 480PT TECHNICAL MANUAL 53 20 NOTE...

Страница 54: ...54 ET8 480 ET8 480S and ET8 480PT TECHNICAL MANUAL 21 NOTE...

Страница 55: ...it 25 9 2 Nadir keyboard 25 10 GENERAL RESET 27 10 1 Reset operations 27 11 USER INTERFACE 28 11 1 General introduction 28 11 2 Led visualization 28 11 3 User and installer log in 29 11 4 User and ins...

Страница 56: ...v 1 0 r 2 0 TECHNICAL MANUAL FEBRUARY 2003 This information and characteristics of the products as described above are not binding on the manufacturer and may be altered without notice EL MO SpA Tel 3...

Отзывы: