Technical Support: +44(0)23 9269 6638 (option 3) 

 

PAK200610_01G   Jan 2021        ©2019 ELMDENE INTERNATIONAL LTD  

 
Fault Diagnostic table 

 Internal - Engineer 

Orange LED 

Diagnostic 

Green LED 

Mains 

Condition 

Possible Cause 

Action 

O

FF

 

O

N

 

Normal 

operation 

Mains present 
Battery fully charged 

None 

O

FF

 

Standby 

Operation 

Mains Lost. No faults present 
Battery driving load 

Investigate loss of mains 

F

LASH 

C

ONTINUOUS

 

O

N

 or O

FF

 

No output 

Output fuse blown 
Output overload 
Output short circuit 

Check and replace 
output fuse 
Disconnect output load 
and test load 

1

 

P

ULSE

 

O

N

 

Battery 

Charging 

No faults active 
Battery charging normally 
but  
< 90% of full charge 

None 

2

 

P

ULSES

 

O

N

 

No Battery 

Battery disconnected 
Battery fuse blown 
Battery heavily discharged 

Check battery 
connections 
Check battery fuse 
Check battery condition 
Replace battery if aged 

O

FF

 

Low Battery 

Volts 

Standby Mode 
Battery almost discharged 

Restore mains 

3

 

P

ULSES

 

O

N

 or O

FF

 

Battery Fault 

High impedance in battery 
connection 
Battery internal fault 

Check battery 
connections for 
corrosion. Replace 
battery if aged 

4

 

P

ULSES

 

O

N

 or O

FF

 

Charger Fault 

Internal failure of battery 
charger 

Return to manufacturer 

5

 

P

ULSES

 

O

N

 or O

FF

 

Battery 

Temperature 

Probe Fault 

Battery temperature monitor 
disconnected or damaged 
PSU running in Safe Mode  

Check temperature 
sensor connections and 
condition of sensor. 
Replace if suspect 

O

C

ONTINUOUS

 

O

N

 or O

FF

 

Internal Fault 

Software fault detected 
PSU running in Safe Mode 

Return to manufacturer 

 

I

NSTALLATION 

 

 

 

This unit is only suitable for installation as permanently connected equipment. The PSU is NOT SUITABLE for 
external installation. 
This unit must be fed from a mains power source having a separate (approved) disconnect device and fitted 
with a fuse or other over-current protection device rated at 5A maximum. Ensure that the disconnect device 
used has appropriate earth fault protection to the applicable standard. 
Where the PSU is used to provide power to a fire alarm circuit,  the mains isolation and disconnect device 

should be provided solely for this purpose and be suitably marked “FIRE ALARM  –

 

DO NOT TURN OFF”. All 

cabling  should  meet  national  and  local  fire  system  installation  regulations,  e.g.  FP200  type  cable  for  high 
integrity installations. 
 
The PSU should be installed according to all relevant safety regulations applicable to the application. 
 
Where  the  PSU  Fault  and  EPS  Fault  outputs  are  used,  they  should  only  be  connected  to  circuits  having 
voltages less than 60V dc. 

Содержание STX2410-MOD

Страница 1: ...eriods Two sets of volt free solid state relay fault outputs signal i loss of mains and ii battery fault charger fault and loss of output In addition there is an RS232 serial interface that can provid...

Страница 2: ...220V With charging Imax A 110V 10 0A 10 0A 8 5A 10 0A 8 0A 7 5A 10 0A 7 2A 6 5A Battery Capacity eg PowerSonic model Yuasa model Interlogix model 2 x 17 18Ah 12V PS12170 NP17 12 BS131N 2 x 38Ah 12V PS...

Страница 3: ...s EPS Fault GEN Fault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mai...

Страница 4: ...n to manufacturer 5 PULSES ON or OFF Battery Temperature Probe Fault Battery temperature monitor disconnected or damaged PSU running in Safe Mode Check temperature sensor connections and condition of...

Страница 5: ...at dissipation and adequate ventilation to avoid overheating of the unit or associated batteries Figure 1 Fixing points COMMISSIONING Mains Power Up 1 With no external connections made to the PSU conn...

Страница 6: ...CT the other two battery terminals to each other 12 Connect the free Positive and Negative terminals of the batteries to the PCB terminals Batt and Batt using the cables provided See Figures 2 3 13 Co...

Страница 7: ...r use by Service Personnel only There are NO USER SERVICEABLE parts inside There is no regular maintenance required of the PSU other than periodic testing and replacement of the standby battery Refere...

Страница 8: ...proved battery disposal route in accordance with all national and local regulations Package used batteries safely for onward transport to your supplier collection point or disposal facility Caution Ri...

Отзывы: