Technical Support: +44(0)23 9269 6638 (option 3) 

 

PAK200610_01G   Jan 2021        ©2019 ELMDENE INTERNATIONAL LTD  

 

C

ONNECTIONS

 

 

 

Load + / -- 

Screw terminals Voltage output to load  

GEN PSU Fault  (normally 
closed contact) 

0.10A @ 60V 

dc 16Ω solid state relay contact

s, volt free 

Open if Mains failed and battery voltage < 23V or fault PSU fault 
condition, (see below) 

EPS Fault  (normally closed 
contact) 

0.10A @ 60V 

dc 16Ω solid state relay contacts, volt free

 

Open if loss of mains for > 10 seconds 

Temperature sensor 

Thermistor input from supplied battery terminal thermistor. 

BATT + / - 

Connection to back up battery using supplied battery lead 

FAN +/ - 

Not used  

RS232 serial interface 

4 pin header   

 

S

IGNALLING AND 

D

IAGNOSTICS

 

 

 
Fault Outputs 

EPS Fault 

GEN Fault 

Condition 

Possible Cause 

Action 

C

LOSED

 

C

LOSED

 

Normal 

operation 

Mains present 
Battery healthy 

None 

O

PEN

 

C

LOSED

 

Standby 

Mode 

Mains lost 
Battery driving load 

Investigate loss of mains 

C

LOSED

 

O

PEN

 

Fault 

Present 

Blown fuses 
Battery fault 
Overload 
Internal fault 

Investigate fault source 
using diagnostic LED 
Rectify fault where 
possible 

O

PEN

 

O

PEN

 

PSU 

Shutdown 

Mains lost 
Standby battery exhausted 

Restore mains as soon 
as possible 

 
LED Indication 

YELLOW LED  

Fault LED 

GREEN LED 

Mains supply On 

DIAGNOSTICS 

Diagnostic LED  

 
Fault Diagnostic table 

 Front panel - User 

Yellow LED 

Fault 

Green LED 

Mains 

Condition 

Possible Cause 

Action 

O

FF

 

O

N

 

Normal 

operation 

Mains present 
Battery healthy 

None 

F

LASH 

C

ONTINUOUS

 

O

or

 

O

FF

 

Fault 

Blown fuses 
Battery fault 
Overload 
Internal fault 

Contact service 
engineer 

1

 

P

ULSE

 

O

FF

 

Standby Mode 

Mains lost 
Battery driving load 

Investigate loss of 
mains 

 

Содержание STX2410-MOD

Страница 1: ...eriods Two sets of volt free solid state relay fault outputs signal i loss of mains and ii battery fault charger fault and loss of output In addition there is an RS232 serial interface that can provid...

Страница 2: ...220V With charging Imax A 110V 10 0A 10 0A 8 5A 10 0A 8 0A 7 5A 10 0A 7 2A 6 5A Battery Capacity eg PowerSonic model Yuasa model Interlogix model 2 x 17 18Ah 12V PS12170 NP17 12 BS131N 2 x 38Ah 12V PS...

Страница 3: ...s EPS Fault GEN Fault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mai...

Страница 4: ...n to manufacturer 5 PULSES ON or OFF Battery Temperature Probe Fault Battery temperature monitor disconnected or damaged PSU running in Safe Mode Check temperature sensor connections and condition of...

Страница 5: ...at dissipation and adequate ventilation to avoid overheating of the unit or associated batteries Figure 1 Fixing points COMMISSIONING Mains Power Up 1 With no external connections made to the PSU conn...

Страница 6: ...CT the other two battery terminals to each other 12 Connect the free Positive and Negative terminals of the batteries to the PCB terminals Batt and Batt using the cables provided See Figures 2 3 13 Co...

Страница 7: ...r use by Service Personnel only There are NO USER SERVICEABLE parts inside There is no regular maintenance required of the PSU other than periodic testing and replacement of the standby battery Refere...

Страница 8: ...proved battery disposal route in accordance with all national and local regulations Package used batteries safely for onward transport to your supplier collection point or disposal facility Caution Ri...

Отзывы: