6
Technical Support: +44(0)23 9269 6638 (option 3)
PAK200609_01F Jan 2021 ©2019 ELMDENE INTERNATIONAL LTD
+
+
Load Output and Remote Signalling
4)
Connect the EPS and GEN PSU Fault outputs to the appropriate inputs of control equipment if remote fault
monitoring is required.
5)
Loop the load (output) wiring through the supplied ferrite EMC suppressor.
Figure 2
–
Connections
6)
Re-apply mains. Verify that the green Mains LED illuminates and the yellow Fault LED flashes after
approximately 3s (disconnected battery).
7)
If connected, verify that the EPS Fault monitor shows a
closed
contact and the GEN PSU Fault monitor
shows an
open
contact.
8)
Perform a full functional test of system including full alarm condition
.
9)
Disconnect mains
.
Figure 3
–
Terminal labels
Standby Batteries
10)
With mains
disconnected,
connect the two 12V standby batteries in series using the single cable provided.
Connect the
negative
of one battery to the
positive
of the other.
DO NOT CONNECT
the other two battery
terminals to each other.
11)
Connect the free Positive and Negative terminals of the batteries to the PCB terminals Batt+ and Batt -
using the cables provided. See Figure 2 and 3.
12)
Connect the battery temperature sensor (two white wires) to the PCB terminals Temp Sense. See Figure 3.
Wires can be connected either way around.
13)
Re-apply mains and, after the LED indicators initial start-up flash, verify that the yellow Fault LED does not
flash (battery connection detected). Verify that the remote PSU Fault monitor shows a
closed
contact.
BATT FUSE
5 Amp
LOAD FUSE
5 Amp
+ - + - GEN EPS Temp
Load Batt Fault
Diagnostic LED
Fault LED
L E N
Mains
Temperature
Sensor connection
+ -
To Load
+
+
-
-