PAK200609_01F   Jan 2021                      ©2019 ELMDENE INTERNATIONAL LTD  

          

+  

 

          

+  

 

Load Output and Remote Signalling 

4)

 

Connect the EPS and GEN PSU Fault outputs to the appropriate inputs of control equipment if remote fault 
monitoring is required. 

5)

 

Loop the load (output) wiring through the supplied ferrite EMC suppressor.  

 

Figure 2 

 Connections 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

6)

 

Re-apply  mains.  Verify  that  the  green  Mains  LED  illuminates  and  the  yellow  Fault  LED  flashes  after 
approximately 3s (disconnected battery). 
 
 

7)

 

If  connected,  verify  that  the  EPS  Fault  monitor  shows  a 

closed

  contact  and  the  GEN  PSU  Fault  monitor 

shows an 

open

 contact. 

8)

 

Perform a full functional test of system including full alarm condition

9)

 

Disconnect mains

 

Figure 3 

 Terminal labels 

 

 
 
 
 
 
 
 

 
 

 
Standby Batteries 

10)

 

With mains 

disconnected, 

connect the two 12V standby batteries in series using the single cable provided. 

Connect the 

negative

 of one battery to the 

positive

 of the other. 

DO NOT CONNECT

 the other two battery 

terminals to each other. 

11)

 

Connect  the  free  Positive  and  Negative  terminals  of  the  batteries  to  the PCB terminals  Batt+  and  Batt  - 
using the cables provided. See Figure 2 and 3. 

12)

 

Connect the battery temperature sensor (two white wires) to the PCB terminals Temp Sense. See Figure 3. 
Wires can be connected either way around. 

13)

 

Re-apply mains and, after the LED indicators initial start-up flash, verify that the yellow Fault LED does not 
flash  (battery connection detected). Verify that the remote PSU Fault monitor shows a 

closed

 contact. 

BATT FUSE 

    5 Amp 

LOAD FUSE 

    5 Amp 

+    -     +    -       GEN     EPS    Temp 
Load     Batt            Fault 

Diagnostic LED 

Fault LED 

L   E  N 

Mains 

 

Temperature 
Sensor connection 

+  -

 

 To Load 

 

Содержание STX2405-MOD

Страница 1: ...ents premature battery failure when operating from standby for extended periods Two sets of volt free solid state relay fault output signal i loss of mains and ii battery fault charger fault and loss...

Страница 2: ...5 0A 5 0 A 5 0A 5 0 A Battery Capacity eg PowerSonic model Yuasa model Interlogix model 2 x 2 1Ah 12V PS12021 NP2 1 12 2 x 7Ah 12V PS12070 NP7 12 2 x 17Ah 12V PS12170 NP17 12 BS131N Battery Charging C...

Страница 3: ...ault GEN Fault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOS...

Страница 4: ...ctive Battery charging normally but 90 of full charge None 2 PULSES ON No Battery Battery disconnected Battery fuse blown Battery heavily discharged Check battery connections Check battery fuse Check...

Страница 5: ...s less than 60V dc Cable Sizing 1 Mains input cable must be to the applicable standard with a 5A or greater current capacity i e 0 75 mm2 nominal conductor area having a minimum operating voltage of 3...

Страница 6: ...Figure 3 Terminal labels Standby Batteries 10 With mains disconnected connect the two 12V standby batteries in series using the single cable provided Connect the negative of one battery to the positiv...

Страница 7: ...contact NOTE Batteries must be connected before mains power is applied to enable the batteries to be utilised When replacing batteries re connect new batteries and then cycle the mains power OPERATING...

Страница 8: ...l regulations Package used batteries safely for onward transport to your supplier collection point or disposal facility Caution Risk of fire or explosion if bare battery wires are allowed to touch See...

Отзывы: