PAK200609_01F   Jan 2021                      ©2019 ELMDENE INTERNATIONAL LTD  

 
 
 
 
 
 
 
 

27.6V dc  5A Switch Mode Power Supply for Fire, Access and General Applications 

STX2405-MOD 

 
 

F

EATURES

 

 

 
The STX2405-MOD is an un-boxed switch mode power supply ideal for use in Fire, Access Control and 
General  Applications.  Its  regulated  27.6V  dc  output  will  supply  up  to  5  Amps  continuously  into  the 
load, in addition to providing up to 850mA for charging the standby batteries up to 17Ah. The power 
supply  output  features  electronic  short  circuit  protection  under  both  mains  and  standby  battery 
operation. Maximum battery life is assured through continuous active battery monitoring and the use 
of  a  two  stage  charger,  comprising  bulk  and  temperature  compensated  final  float  phase  depending 
upon battery condition. Once fully charged the product operates in Eco power saving mode, whereby 
the batteries are charged for 4 hours in every 24 hour period while still being continuously monitored. 
This reduces wasted energy in charging already fully charged batteries and extends their working life. 
Deep  discharge  protection  prevents  premature  battery  failure  when  operating  from  standby  for 
extended periods. Two sets of volt free solid state relay fault output, signal (i) loss of mains and (ii) 
battery fault, charger fault and loss of output.  
 
 

 

Up to 5A current to load at 27.6V dc nominal regulated output. 

 

Charging capability to support 7 or 17Ah batteries. 

 

Electronic overload protection shuts down output until overload or short circuit is removed. 

 

Battery Monitor detects battery missing, low battery, short-circuit, reverse connection or circuit 
impedance (Ri) in excess of 300m

 caused by connector or wiring  corrosion. 

 

Battery charging circuit is energised only when a battery is correctly connected and the battery 
voltage is greater than 14V. 

 

No loss of output during automatic connection of battery to load on loss of mains. 

 

Deep discharge protection disconnects battery from load when battery voltage level falls below 
21V. 

 

Internal diagnostic indicator LED (Orange). 

 

Fault indicator LED (Yellow) flashes on detection of output fault, battery fault, charger fault and 
mains failure. 

 

Mains indicator LED (Green) showing mains present Indicators check at start-up. 

 

                

 

 
Elmdene International Ltd

 

 

Tel:  +44(0)23 9269 6638 

3 Keel Close, Interchange Park, 

 

Fax:  +44(0)23 9266 0483 

Portsmouth, Hampshire, PO3 5QD, UK 

Web:   

www.elmdene.co.uk

 

0843-CPR-0215 14 (UL) 

2531-CPR-CSP11214 20 (DBI) 

Содержание STX2405-MOD

Страница 1: ...ents premature battery failure when operating from standby for extended periods Two sets of volt free solid state relay fault output signal i loss of mains and ii battery fault charger fault and loss...

Страница 2: ...5 0A 5 0 A 5 0A 5 0 A Battery Capacity eg PowerSonic model Yuasa model Interlogix model 2 x 2 1Ah 12V PS12021 NP2 1 12 2 x 7Ah 12V PS12070 NP7 12 2 x 17Ah 12V PS12170 NP17 12 BS131N Battery Charging C...

Страница 3: ...ault GEN Fault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOS...

Страница 4: ...ctive Battery charging normally but 90 of full charge None 2 PULSES ON No Battery Battery disconnected Battery fuse blown Battery heavily discharged Check battery connections Check battery fuse Check...

Страница 5: ...s less than 60V dc Cable Sizing 1 Mains input cable must be to the applicable standard with a 5A or greater current capacity i e 0 75 mm2 nominal conductor area having a minimum operating voltage of 3...

Страница 6: ...Figure 3 Terminal labels Standby Batteries 10 With mains disconnected connect the two 12V standby batteries in series using the single cable provided Connect the negative of one battery to the positiv...

Страница 7: ...contact NOTE Batteries must be connected before mains power is applied to enable the batteries to be utilised When replacing batteries re connect new batteries and then cycle the mains power OPERATING...

Страница 8: ...l regulations Package used batteries safely for onward transport to your supplier collection point or disposal facility Caution Risk of fire or explosion if bare battery wires are allowed to touch See...

Отзывы: