Technical Support Line +44 (0)23 9269 6638 (Option 3) 

PAK200360 Iss 03B   Mar 2012 

©2012 ELMDENE INTERNATIONAL LTD 

 

O

PERATION

 

 

 

The 

Quartz 

sounder is used for notification of an alarm condition as generated within an intruder, hold-

up or other alarm system. In response to commands from the alarm system control panel, the 

Quartz 

will 

emit a high intensity sound and/or operate a visual flash. 

 

 

The 

Quartz 

will detect any attempt to gain unauthorised access to the sounder by removal of the cover, 

or any attempt to remove it away from its mounting surface. This will generate a tamper signal which is 
normally fed back to the alarm control panel.   
 

 

The 

Quartz 

is classified a self powered sounder and has an on-board battery which is recharged via the 

external power source. This battery is used to operate the sounder if the external power is removed. The 

Quartz 

can be configured to self actuate (SAB Mode ON) in the event that a tamper condition is detected 

or the external power to the sounder is removed. 

 

To assist with commissioning, the 

Quartz

  has an Engineer Mode to provide silent start-up. Two Comfort 

LEDs are used to provide a heart-beat type visual indication when the 

Quartz

  is not sounding.  

 

F

UNCTIONAL 

I

NFORMATION

 

 

 

Tamper Circuit for Single or Multiple Cascade Installations 

For single sounder installations link TS to H- and connect TR to the control panel Tamper Return input. 
(See Fig. 2). 
In cascade installations with two or more sounders, the TS (Tamper Source) will normally be connected 
to the TR (Tamper Return) of the next sounder except for the last unit which will have TS linked to H-. 
(See Fig. 3) 

 

Engineer Mode 

This selects silent start-up and silent maintenance. The ENG input may be brought back to the control 
panel and connected to a programmable output. Switching this control panel output high when 
maintenance is required will prevent the sounder from self activating when the cover is removed or R- 
activated. The Tamper output is open when ENG is high, this prevents inadvertent system setting with 
the sounder left in Engineer Mode (when SAB Mode = on). 

 

O

PTIONS 

S

ELECTION

 

 

 

Sound Cut-off Timer 

The 

Quartz 

sounder will automatically stop sounding after the time period selected by the Sound Cut-off 

Timer link, Figure 11, irrespective of the status of the sound trigger (R-) input.  The 5s option is provided 
to reduce nuisance noise during testing. 

 

SCB/SAB Mode 

In SAB mode the sounder can draw current from both the control panel and the battery. The siren will 
self-activate if either of the tampers are activated. 

 

In SCB mode the sounder draws the majority of its current from the battery to minimise drain on the 
control panel. This allows the user to connect multiple units to a control panel without overloading it. 
Select SCB mode using the link next to the terminal blocks (Figure 1.0). In this mode the sounder will NOT 
self activate under a tamper condition but the tamper condition will still be signalled back to the control 
panel. The control panel can then trigger the siren using the R– line.  

 

 

Note: The siren will self-activate if the supply lines are cut in either mode. 
 
 

 

 

 

             

 

 

          

Содержание QUARTZ-1000-G2

Страница 1: ...ounding Silent Engineer Start up Selectable sound auto cut off timer Selectable SAB or SCB operating mode Integral 1 Watt Xenon tube strobe Active inrush current limit on strobe Strobe Power Save Mode...

Страница 2: ...he TS Tamper Source will normally be connected to the TR Tamper Return of the next sounder except for the last unit which will have TS linked to H See Fig 3 Engineer Mode This selects silent start up...

Страница 3: ...ation or maintenance In engineer test mode apply a positive signal to prevent self activation of siren by tamper condition e g lid open H Permanent positive hold off supply H Permanent negative hold o...

Страница 4: ...8 Option 3 PAK200360 Iss 03B Mar 2012 2012 ELMDENE INTERNATIONAL LTD Fig 2 Single Quartz Tamper Connection ENG H H TS TR R ST TAMP IN ST R H H TS ST TR R H H ENG CONTROL PANEL UNIT 1 UNIT 2 Fig 3 Mult...

Страница 5: ...holes as required for fixing the backplate to the wall and for cable entry to the rear of the unit 3 Fit tamper extender if required and trim to desired length 4 Route cable from control panel throug...

Страница 6: ...store H 17 Disconnect H and check that the siren activates Restore H 18 Commissioning complete MAINTENANCE The Quartz sounder should be tested for correct operation on a periodic basis A minimum of on...

Страница 7: ...sounders on one tamper loop Cover or Rear tamper switch not closed Check cover and rear tamper switches fully closed DISPOSAL OF PRODUCT AT END OF LIFE This product falls within the scope of EU Direc...

Страница 8: ...Ni MH Voltage 6 0V Capacity 320 mAH Strobe Rating 1 Watt Flash Rate 1 Hz reduces to 1 2 Hz after 15 minutes Comfort LEDs Alternate flash 60 per minute Material 3mm Polycarbonate all parts Tamper Detec...