background image

2

 

 

 

 

Technical Support: +44(0)23 9269 6638 (option 3) 

  PAK200033_05A   Jan 2012                        ©2012 ELMDENE INTERNATIONAL LTD  

 

The tamper return output to the control may be configured using link JP1 jumper for either: 

-

 

Switched output: 

Tied to 0V in tamper non-active condition. 

 

 

 

 

HIGH (6.0 - 7.5V) in tamper active condition 

-

 

Open collector output:   Pulled to 0V when in non-tamper state 

 

M

ODE 

S

ELECTION

 

 

 
JP1 

Negative tamper enable. 

 

Link pins 1 & 2 for switched output (default). 

 

Link pins 2 & 3 for open collector o/p 

JP2 

Cut-off timer. 

 

Link = no cut-off (default) 

 

No link = sounder cut-off after 15 minutes 

JP3 

Siren tone. 

 

Link = fast whoop (default) 

 

No link = warble 

 

 

Figure 1.0 Connections and Jumper Link Options 

S

OUND 

C

UT

-O

FF 

T

IMER

 

 

 

With the cut-off timer link NOT fitted, the 

INT500(S)

 sounder will automatically stop sounding after 15 

minutes, irrespective of the status of the sound trigger (R-) input.  

 

SAB

 

M

ODE 

(INT500S

 

O

NLY

 

 

SAB mode is enabled if the internal battery is connected. The siren will self-activate if either of the 
tampers are activated.  The INT500S will also self-activate if the supply lines are cut. 

 

C

ONNECTIONS

 

 

 

R-

 

Negative siren trigger. Apply 0V to activate sounder 

M-

 

Negative low volume siren trigger (keypad). Apply 0V to activate. 

ST-

 

Negative strobe trigger. Apply 0V to activate strobe. 

H+

 

Permanent positive hold-off supply, +12Vdc nominal 

H-

 

Permanent negative hold-off supply 

RTN

  Negative tamper return. 

BAT-

  SAB Battery negative

  

BAT+

  SAB Battery positive

 

 

C

OMMISSIONING

 

 

 

1) 

Remove cover. 

 

2) 

Offer backplate to desired position on 
mounting surface and drill holes to match 
chosen fixing centres. 

3) 

Fix backplate to mounting surface using 
appropriate fixings for the mounting surface. 

4) 

Set the required Cut-off Timer, Tamper Return options and Siren Tone using JP1,  JP2 and JP3. 

5) 

Loop the connection cable three times through the supplied ferrite as shown. 

6) 

C12V dc and 0V supply from the control panel to H+ and H- respectively. 

JP3 

JP2 

JP1 

VR1 

R-  M- ST-  H+  H-  RTN

 

BAT+ BAT

   

.      .  

   

.      .  

   

.      .    .  

Отзывы: