Technical Support: +44(0)23 9269 6638 (option 3) 

  PAK200545_03B May 2016                        ©2016 ELMDENE INTERNATIONAL LTD  

Fold up ‘Tabs’ to locate 
battery and secure with 
the rubber band supplied 

Fold up ‘Tabs’ to locate 
battery and secure with the 
rubber band supplied 

 
 

         

                             

 

 
 
 
 

            Fig 3   GEN2-18-B 

 

      

               Fig 4   GEN2-08-B 

 
 
 

   

      

                        

 

 
 
 

            Fig 5   GEN2-18-C 

 

 

               Fig 6   GEN2-08-C 

 
14)

 

Apply mains power. 

Check that Green Mains LED is ON. 
Check there is no fault indicated by the Red Fault LED, refer to diagnostic table on page 6. 

15)

 

Disconnect mains power. 

Check that the batteries continue to supply voltage and current to the output load. 
Check that Green Mains LED is OFF and the control panel displays a Loss of Mains (EPS) fault 

NOTE:

 Batteries must have sufficient charge to supply the output load 

16)

 

Reconnect mains power. 

Check that Green LED is ON. 

17)

 

Remove Output fuse. 

Check that Red Fault LED is indicating a fault, refer to diagnostic table on page 6, and that the 
control panel shows a General PSU fault. 

18)

 

Replace Output fuse. 

Check that Red Fault LED is OFF and General PSU fault has cleared at control panel. 

Battery 

Battery 

Battery 

Fold up ‘Tabs’ to locate 
battery and secure with 
the rubber band supplied 

Fold up ‘Tabs’ to locate 
battery and secure with 
the rubber band supplied 

Battery 

Содержание GEN2-08 Series

Страница 1: ...a false loss of mains alarm Two LEDs assist with quick and easy installation by showing presence of mains correct battery charging and a fault condition Comprehensive protection is built in as standar...

Страница 2: ...x 200 x 80 355 x 330 x 80 330x 275 x 80 Weight kg excluding battery 2 0 4 0 3 3 Material 1 2mm steel white powder coated Environmental Temperature 10 to 40 C operating 75 RH non condensing 20 to 80 C...

Страница 3: ...mains fail Open if loss of mains GEN Fault Relay output for General Fault Open in fault condition BATT Connection to standby battery Use cables provided Observe polarity INSTALLATION AND COMMISSIONING...

Страница 4: ...rectly rated load cable through supplied ferrite 1 turn and attach to terminal block note polarity Fasten with cable ties Fig 2 Position of ferrite 9 Apply mains power Check Green Mains LED is ON NOTE...

Страница 5: ...ntinue to supply voltage and current to the output load Check that Green Mains LED is OFF and the control panel displays a Loss of Mains EPS fault NOTE Batteries must have sufficient charge to supply...

Страница 6: ...er retaining feature engaging over the bottom lip of the base fasten with screws supplied 21 Check that the tamper switch is CLOSED when the lid cover is closed and the retaining screws are fitted OPE...

Страница 7: ...E parts inside There is no regular maintenance required of the PSU other than periodic testing and replacement of the standby battery Reference should be made to the battery manufacturer s documentati...

Страница 8: ...WEEE and 2013 56 EU Battery At the end of life the product must be separated from the domestic waste stream and disposed via an appropriate approved WEEE disposal route in accordance with all national...

Отзывы: