Standby Battery 

11)

 

Attach supplied battery cables to terminal block and batteries. 

NOTE:

 ensure correct polarity of battery connections: 

Red

 lead to 

+ve

 of 

battery

 

1

Black

 lead to   

-ve

 of 

battery 2

. Connect 

-ve

 of 

battery 1

 to 

+ve

 of 

battery 2

 using short link lead  

12)

 

Position batteries to avoid lid fixing screw. 

13)

 

Apply mains power. Check Green Mains LED is ON. 

14)

 

Check there is no fault indication on Yellow Fault LED. 

15)

 

Disconnect mains power. Check that the batteries continue to supply voltage and current to the 
load. Check Green Mains LED is OFF.

 

NOTE

: Batteries must have sufficient charge to supply the load 

16)

 

Reconnect mains power. Check Green Mains LED is ON. 

17)

 

Remove Load fuse and check Yellow Fault LED is ON. 

18)

 

Replace Load fuse. Check Yellow Fault LED is OFF. 

 

M

ODEL 

S

PECIFICATION 

T

ABLE

 

 

 

 

G2401N 

G2402N 

G2403N 

G2405N 

Output Current 

1A 

2A 

3A 

5A 

Battery Charge Current 

0.5A 

0.5A 

0.5A 

0.5A 

Mains LED (Green) 

 

 

 

 

Fault LED (Yellow) 

 

 

 

 

Max Mains Input Current 

(at 90Vac)

 

1.0A 

1.3A 

1.4A 

2.0A 

F1 - Mains Input Fuse (20mm HRC) 

T2.0A 

T2.0A 

T3.15A 

T3.15A 

F2 - Output Fuse (20mm) 

F1.0A 

F2.0A 

F3.15A 

F5.0A 

F3 - Battery Fuse (20mm) 

630mA 

630mA 

630mA 

630mA 

 
 

O

PERATING 

I

NSTRUCTIONS

 

 

 

This unit is intended for use by Service Personnel only - There are NO USER SERVICEABLE parts inside. 

 

The  Green  Mains  LED  will  be  illuminated  whilst  the  mains  supply  is  present.  In  the  event  of  a  fault 
condition, the Yellow  Fault LED will be illuminated. 

 
 
 
 
 
 
 
 
 

10cm all round  

.


10cm all round  

.

L E N 

10cm all round  

.