background image

     

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

27.6V

DC 

S

WITCH 

M

ODE 

P

OWER 

S

UPPLIES 

 

W

ITH 

R

EMOTE 

F

AULT 

S

IGNALLING

 

Models:

 

G240xN-y 

Where ‘x’ is max load current  and ‘y’ is Enclosure type

 

 

F

EATURES

 

 

High efficiency cost effective power supply ideal for use in Fire, Access Control and General Security 
applications. Featuring a regulated 27.6Vdc output supplying continuous full rated current to load and up to 
an additional 0.5A for charging 2 x 12V standby batteries, if fitted. The universal mains input voltage enables 
the power supply to be used across a wide geographical area. The highly efficient switch mode design ensures 
low operating costs, generates less heat and with a small physical size increases the room available for 
additional PCBs or cables. The modular construction simplifies maintenance. 

 

Continuous full rated current to load 

 

Modular construction for ease of maintenance 

and installation 

 

Additional 0.5A to charge 2 x 12V standby 
batteries 

 

Full electronic short circuit and overload 

protection on load output under mains 
operation 

 

Universal mains input voltage 90-264Vac 

 

Mains transient protection circuit 

 

High efficiency electronics for reduced running 
costs and lower operating temperatures 

 

Green Mains present LED 

 

Installer safe design with all high voltage 
electronics fully shrouded 

 

Yellow Fault LED 

 

Reverse battery connection protection 

 

 

 

 

 

 

S

PECIFICATION

 

 

Input Specification 

Voltage (rated) 

100-240Vac 

Voltage (operating) 

90-264Vac 

Frequency  

50-60Hz 

Max Current 

See Model Specification Table  

Mains Input Fuse 
Max standby Power 

See Model Specification Table 
0.8W (No load and no battery connected) 

Output Specification 

Voltage 

27.0 – 28.0Vdc (27.6Vdc nominal) on mains power 
21.0 – 24.7Vdc on battery standby 

Max load current 

See Model Specification Table 

Ripple 

100 mV pk-pk max 

Load output Fuse 

See Model Specification Table below  

Overload 

Electronic shutdown until overload or short circuit removed 
(under mains power only) (G2403N & G2405N) 
Fuse Protection (G2401N & G2402N) 

www.acornfiresecurity.com

www.acornfiresecurity.com

Отзывы: