Local
Indicators
MAINS LED (Green)
Mains present
Mechanical
Chassis Dimensions (mm)
127 x 65 x 160 (w x h x l)
Fixing holes
4 x Ø4.0mm on 132 x 119 pitch
Environmental
Temperature
-10 to +40°C (operating) 95% RH non-condensing
-20 to +80°C (storage)
Connections
LOAD+
+ve voltage output to load equipment
LOAD-
-ve voltage output to load equipment
BATT+ and -
+ve (Red lead) and -ve (Black lead) connections to standby
battery
Installation and Commissioning Instructions
This unit is only suitable for installation as permanently connected equipment. The PSU is
NOT
SUITABLE
for external installation
. EQUIPMENT MUST BE EARTHED
. Before installation, ensure
that external disconnect device is
OFF
. Install according to all relevant safety regulations applicable
to the application.
Mounting
1)
Mount chassis securely using mounting holes.
Mains Power Up
2)
Attach correctly rated mains cable (minimum 0.5mm2 [3A], 300/500Vac) between external
approved disconnect device and mains input terminal block. Ensure disconnect device has
earth fault protection.
3)
Fasten mains cable to chassis using cable ties.
4)
Apply mains power. Check for 13.8vdc on load outputs. Check green Mains LED is on.
5)
Disconnect mains power.
Load Output
6)
Attach correctly rated load cable and fasten in place using cable ties. Note polarity.
7)
Apply mains power. Check green Mains LED is on.
8)
Disconnect mains power.
Standby Battery
9)
Attach supplied battery cables to battery.
NOTE
: ensure correct polarity of battery connections:
+ve
use
red
lead,
-ve
use
black
lead.
10) Check that the batteries supply voltage and current to the load.
NOTE
: batteries must have sufficient charge to supply the load
11) Apply mains power. Check green Mains LED is on.
12) Using a meter set to its current measurement range, check for charging current flow
into
battery.
Operating Instructions
This unit is intended for use by Service Personnel only - There are NO USER SERVICEABLE parts
inside.
The green Mains LED will be illuminated whilst the mains supply is present.