1 / 2
PRI-32
cos φ ≥ 0.95
M
M
HAL.230V
K
M
M
AC12
250V / 1A
DC14
x
AC1
250V / 8A
AC13
x
AC2
250V / 3A
AC14
250V / 3A
AC3
250V / 2A
AC15
250V / 3A
AC5b
300W
DC5
24V / 2A
AC6a
x
DC12
24V / 8A
AC7b
250V / 1A
DC13
24V / 2A
02-5/2017 Rev.: 1
DC1
24V / 8A
DC3
24V / 3A
15
16 18
A1
A2
< I
A1 A2
15 18
16
Un
1
4
2
3
6
5
Made in Czech Republic
ELKO EP, s.r.o.
Palackého 493
769 01 Holešov, Všetuly
Czech Republic
Tel.: +420 573 514 211
e-mail: [email protected]
www.elkoep.com
Monitoring current relay
Characteristics
Description
Symbol
Connection
Type of load
Mat. contacts AgNi,
contact 8A
Type of load
Mat. contacts AgNi,
contact 8A
AC5a
uncompensated
230V / 1.5A (345VA)
AC5a
compensated
x
EN
•
current transformer is a part of the product. Inside this transformer there is a wire
which senses the volume of fl owing current
•
this construction lowers temperature straining of the product when compared
with conventional solution with in-built shunt. Increases current range up to 20 A
and galvanically separated measured circuit
•
for hetaing bars in sliding rails, heating cables, indication of current fl ow, control-
ling of 1-phase motor consumption...
•
fl uent adjusting actualing current via potentiometer 1 - 20 A
•
universal supply AC 24 - 240 V and DC 24 V
•
current exceeding - current fl owing through monitored wire must not exceed
100 A
•
output contact: 1x changeover / SPDT 8 A
•
clamps terminal
•
1-phase, 1-MODULE, DIN rail mounting
1. Supply voltage terminals
2. Output indication
3. Adjustmentod of access current
4. Supply indication
5. Controlling cable outlet (max. Ø 6 mm)
6. Output contacts